General Data, 200 V Converters - Siemens SINAMICS G120 Installation Manual

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
6.4 200 V converters
6.4.1

General data, 200 V converters

Property
Line voltage
Line supply configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category
according to EN 61800-5-
1
Pulse frequency
Short-circuit current
(SCCR) and branch pro-
tection
Degree of protection ac-
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection accord-
ing to EN 50274
Cooling in compliance with
EN 60146
Safety Integrated
78
Version
FSA ... FSC
200 V ... 240 V 1 AC ± 10%
200 V ... 240 V 3 AC ± 10%
FSD ... FSF
200 V ... 240 V 3 AC ± 10% (in
operation -20% < 1 min)
Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 46)
FSA ... FSC
2% ≤ Uk < 4%. For Uk < 2%, we recommend a line reactor, or a Power Mod-
ule with the next higher power rating.
FSD ... FSF
No restrictions
FSA ... FSC
0.7 without line reactor for Uk ≥ 2%
0.85 with line reactor for Uk < 2%
FSD ... FSF
> 0.9
0 V 3 AC ... 0.95 × input voltage
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
4 kHz (factory setting),
Adjustable in steps of 2 kHz.
Current reduction as a function of the pulse frequency (Page 86)
If you increase the pulse frequency, the converter reduces the maximum output current.
Maximum permissible line short-circuit current ≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
IP20
IP55
PT devices outside the control cabinet
The converters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
See function manual "Safety Integrated"
"Safety Integrated" function manual
(https://support.industry.siemens.com/cs/ww/en/view/109751320)
0.55 kW ... 4 kW - LO
0.37 kW ... 3 kW - HO
0.55 kW ... 7.5 kW - LO
0.37 kW ... 5.5 kW - HO
11 kW ... 55 kW - LO
7,5 kW ... 45 kW - HO
Hardware Installation Manual, 01/2020, A5E33294624B AL
Power Module PM240-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics pm240-2

Table of Contents