Siemens SINAMICS G120 Installation Manual page 93

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Table 6- 18
PM240-2, IP20, frame size B, 380 V ... 480 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
Table 6- 19
PM240-2, PT, frame size B, 380 V ... 480 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
1) approx. 0.16 kW through the heatsink
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
6SL3210-1PE21-1UL0
6SL3210-1PE21-1AL0
4.0 kW
13.3 A
10.2 A
3.0 kW
11.6 A
7.7 A
3NA3812 (32 A)
35 A
0.11 kW
9.2 l/s
2.9 kg
3.1 kg
6SL3211-1PE21-8UL0
6SL3211-1PE21-8AL0
7.5 kW
22.2 A
18.0 A
5.5 kW
19.8 A
13.7 A
3NA3812 (32 A)
35 A
0.2 kW
1)
9.2 l/s
3.6 kg
3.9 kg
6SL3210-1PE21-4UL0
6SL3210-1PE21-4AL0
5.5 kW
17.2 A
13.2 A
4.0 kW
15.3 A
10.2 A
3NA3812 (32 A)
35 A
0.15 kW
9.2 l/s
2.9 kg
3.1 kg
Technical data
6.5 400 V converters
6SL3210-1PE21-8UL0
6SL3210-1PE21-8AL0
7.5 kW
22.2 A
18.0 A
5.5 kW
19.8 A
13.2 A
3NA3812 (32 A)
35 A
0.2 kW
9.2 l/s
3.0 kg
3.2 kg
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics pm240-2

Table of Contents