Accessories
8.12 dv/dt filter plus VPL
Article number JTA: TEF1203
Rated power
Rated voltage (phase to phase)
Rated output current (rms)
Maximum output current (rms)
Inductance (Tolerance ± 5%)
Winding resistance
Nominal pulse frequency
Maximum pulse frequency
Output current maximum pulse fre-
quency
Maximum output frequency
Voltage drop
Rated DC link voltage
Maximum voltage rise at motor ter-
minals
1)
Maximum peak voltage at motor
terminals (phase to phase)
Maximum peak voltage at motor
terminals (phase to earth)
Maximum cable length filter - motor
(screened / unscreened)
Terminal type
Rated terminal cross section (load
circuit)
Rated terminal cross section (DC
link feedback)
4)
Degree of protection
5)
Ambient temperature
6)
Weight
Connection
Line / motor cable
DC link
Ground
Voltage rise according IEC/TS 60034-17
1)
Under nominal DC link voltage
2)
Maximum peak voltage at motor terminals < 1350V at cable length up to 450m screened or 650m unscreened Maximum
3)
peak voltage at motor terminals < 1500V at cable length up to 525m screened or 800m unscreened
Short-circuit-proof wiring is required
4)
Installing the filter in an enclosure is required
5)
Higher ambient temperatures up to 60°C allowed with current derating at 40°C, in the range 40...50°C with 1.5% per 1K
6)
and in the range 50...60°C with 1.9% per 1K
162
-0KB
90 kW
690 V (+10%)
103 A
160 A
0.53 mH
3 x 4.9 mΩ
2 kHz
4 kHz
61.8 A
150 Hz
17.2 V
935 V
< 500 V/μs
1350 V ... 1500 V
2) 3)
1100 V
2)
450 m / 650 m
3)
525 m / 800 m
Busbar M8
95 mm²
25 mm²
IP00
-20°C to 40°C
77 kg
95 / 13.0
3/0 / 115
25 / 9.0
4 / 80
50 / 6.0
1 / 53
-0LB
132 kW
690 V (+10%)
230 A
70 A
0.37 mH
3 x 3.25 mΩ
2 kHz
4 kHz
87.6 A
150 Hz
17.1 V
935 V
< 500 V/μs
1350 V ... 1500 V
1100 V
450 m / 650 m
525 m / 800 m
Busbar M10
120 mm²
25 mm²
IP00
-20°C to 40°C
97 kg
Metrical (mm² / Nm)
Imperial (AWG / lbf.in)
120 / 13.0
4/0 / 115
25 / 9.0
4 / 80
70 / 6.0
2/0 / 53
Hardware Installation Manual, 01/2020, A5E33294624B AL
-0MB
250 kW
690 V (+10%)
416 A
104 A
0.22 mH
3 x 1.4 mΩ
2 kHz
4 kHz
156 A
150 Hz
18.0 V
935 V
< 500 V/μs
1350 V ... 1500 V
1100 V
450 m / 650 m
525 m / 800 m
Busbar M10
2x120 mm²
1x185 mm²
50 mm²
IP00
-20°C to 40°C
172 kg
2 x 120 / 13.0
2 x 4/0 / 115
185 / 13.0
6/0 / 13.0
50 / 9.0
1 / 80
95 / 6.0
3/0 / 53
Power Module PM240-2