Table 6 Alarm Signals - Pulsar Plus - GE Infinity M Series Installation Manual

High capacity with horizontal distribution, 13 u system with galaxy pulsar plus controller, 22u system with galaxy millennium ii controller, initial/supplemental frame, 22u system with supplemental frame and galaxy millennium ii controller
Table of Contents

Advertisement

NE-M Installation Guide
Step
Connect and wire remote alarm output circuits to Connector J4. J4 is output alarm connector.
Utilize cable as necessary to obtain the desired connections to the outputs shown below.
Output Alarm Cable comcodes for J4 are: 50ft: CC848817635, 150ft: CC848817643.
Pin
Wire
1
BL
2
O
3
G
4
4
W
5
BK
6
BL/W
7
O/R
8
G/W
9
W/R
10
BK/R
Connect to network.
The controller provides an Ethernet connection for a LAN and or Craft port connection. Connector J5 provides a
standard RJ45 shielded receptacle connection for a standard Cat-5 connection to the controller's 10/100Base-T
5
port. This port has two main modes of operation: Server mode, LAN mode (Static and DCHP Client). In server
mode, the port can be used as a local Craft interface. In this mode, a local laptop can be connected through J5
and its standard web browser used to directly access the controller by typing in network address
http://192.168.2.1. A connection should never be made between the controller and LAN while the controller is in
Server mode.
Yes – go to Step 6.
19
Relays are reconfigured for specific use for specific Eco applications.
850050111
Issue 03 August 2017
Action – Pulsar Plus
Output Alarm Connector

Table 6 Alarm Signals - Pulsar Plus

Signal
Pin
Wire
Name
19
PCR
11
BL/BK
PMJ
12
O/BK
PMN
13
G/BK
UR1
14
W/BK
UR2
15
BK/W
UR3
16
BL/R
UR4
17
R
UR5
18
R/G
UR6
19
R/W
UR7
20
R/BK
Network (LAN) Connection (Optional)
Is the controller equipped with the Modem Option?
Defaults
Signal
Name
19
Standard
PCR
PCR_C
(Power Critical)
PMJ
PMJ_C
(Power Major)
PMN
PMN_C
(Power Minor)
BD
UR1_C
(Battery on
Discharge)
VLV
UR2_C
(Very Low Voltage)
FAJ
UR3_C
(External Fuse Major)
ACF
UR4_C
(rectifier input AC or
DC) Fail)
RFA
UR5_C
(Rectifier Fail)
MRFA
UR6_C
(Multi Rectifier Fail)
HV
UR7_C
(High Voltage)
No – go to Step 7.
H5692448
Eco
Generator
Start/Stop
Generator
Maintenance