Connect Interframe Bus Bars; Figure 19 Interframe Bus Bars - GE Infinity M Series Installation Manual

High capacity with horizontal distribution, 13 u system with galaxy pulsar plus controller, 22u system with galaxy millennium ii controller, initial/supplemental frame, 22u system with supplemental frame and galaxy millennium ii controller
Table of Contents

Advertisement

NE-M Installation Guide

Connect Interframe Bus Bars

Step
Return Bus
Primary Bus
5/16" Hardware
3/8" Hardware
WARNING: Energy
Bus bars of systems with powered rectifiers or batteries connected provide hazardous
electrical energy.
Yes – go to Step 1.
Verify AC power is OFF and Batteries are disconnected.
Use appropriate lock-out tag-out procedures before continuing.
1
• Turn all AC breakers off and lock-out tag-out.
• Disconnect all batteries.
Attach 850046677 Link Buses  to Primary voltage-buses and Return buses in both cabinets (4 places).
2
Secure with 3/8" hardware provided – Torque to 240 in-lb (27 Nm) – 9/16" socket.
Attach T-Bus bars  &  as shown (4 places).
3
Secure with 5/16" hardware provided – Torque to 160 in-lb (18 Nm) – 1/2" socket.
Attach Interframe Bus bars  as shown (2 places).
4
Secure with M8 hardware provided – Torque to 160 in-lb (18 Nm) – 1/2" socket.
Cover Interframe Bus bars with two 848414611 Lexan Covers .
5
Remove paper covering on covers before installing.
850050111
Issue 03 August 2017
Return Bus
Interframe Buses - Front View
Primary Bus
Rear View

Figure 19 Interframe Bus Bars

Are Initial Frame rectifiers ON or batteries connected?
Action
Primary Bus
Return Bus
Rear View
No – go to Step 2.
 848414611 Lexan Cover (2)
 8500051755 Interframe Bus (2
 847760204 T-Bus Return (2)
 847760196 T-Bus -48V (2)
 850046677 Link Bus (4)
5/16" Hardware
3/8" Hardware
H5692448