Connect Batteries; Connect Tray Mounted Batteries; Figure 43 Battery Disconnect Switch; Figure 44 Batt Disconnect Switch Input Bus - GE Infinity M Series Installation Manual

High capacity with horizontal distribution, 13 u system with galaxy pulsar plus controller, 22u system with galaxy millennium ii controller, initial/supplemental frame, 22u system with supplemental frame and galaxy millennium ii controller
Table of Contents

Advertisement

NE-M Installation Guide

Connect Batteries

Connect Tray Mounted Batteries

Go to the procedure for the disconnect method provided on the trays:
Battery Disconnect Switch Connection
Anderson Connector Connection
Direct to Battery Bus Connection
Battery cables from factory mounted battery trays are factory installed and terminated to the distribution panel.
Battery Disconnect Switch Connection
Step
Ensure disconnect switch is in the OFF position
(downward) prior to making any connections.
1
Remove the two 6/32 screws to remove the
plastic cover.
Connect one end of the 2/0 cable to the input bus
of the disconnect switch with 1/4-20 hex nuts
provided.
2
Torque to 65 in-lb – 7/16" socket.
Re-attach clear plastic cover to disconnect
3
switch and secure with 6-32 screws.
850050111
Issue 03 August 2017
Action

Figure 43 Battery Disconnect Switch

Input Bus

Figure 44 Batt Disconnect Switch Input Bus

H5692448
Disconnect
Switch
35