GE Infinity M Series Installation Manual page 76

High capacity with horizontal distribution, 13 u system with galaxy pulsar plus controller, 22u system with galaxy millennium ii controller, initial/supplemental frame, 22u system with supplemental frame and galaxy millennium ii controller
Table of Contents

Advertisement

NE-M Installation Guide
Pulsar Controller Status
Millennium Controller
Display
Status Display
MAJ Major
Communication Fail
BD
AC
DC
green green green
-54.48V1 1000A
FLOAT
Display Red
MIN Clock Battery Low
BD
AC
DC
Minor
green green green
amber
-54.48V1 1000A
FLOAT
Display Amber
850050111
Issue 03 August 2017
Rect/
Dist.
Conv
Module
LED
LEDs
Major
Norm
red
Red
green
blink
Controller
Norm
amber
green
green
Possible Problem(s)
• LVD Board lost communication
with the controller.
• Multiple devices no longer
communicating with the
controller.
Controller Clock Battery Is Low.
Possible Solution(s)
1. Clear blinking red LEDs on all devices.
See other conditions with blinking red LEDs.
2. Correct communication with each device.
3. Issue the Menu > Control / Operations > Uninstall
Equipment command.
(This only removes this alarm for unconnected devices.)
4. Replace Distribution Module Board.
5. If problem persists, call your local field representative.
1. Replace the Controller Clock Battery.
2. If problem persists, call your local field representative
H5692448
76

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ne-m seriesH5692448

Table of Contents