NE-M Installation Guide
Step
Configure alarm relays to "Open On Alarm" or "Close On Alarm" as specified in site engineering instructions.
Each Alarm Relay Jumper select "Open On Alarm" or "Closed On Alarm" for one alarm signal and each signal
output can be configured independently.
Carefully move each Alarm Relay Jumper to select "Open On Alarm" or "Close On Alarm" position as per site
engineering instructions with an insulated tool.
The following table contains the alarms along with the factory default alarm assignments to user relays R1-
R7.
3
Utilize the web interface to change any of the alarm user relay alarm assignments.
4
Yes – go to Step 5.
850050111
Issue 03 August 2017
Action – Pulsar Plus

Figure 70 Alarm Relay Jumper Positions - Pulsar Plus

Table 3 Alarm Defaults – Standard Pulsar Plus
Jumper
Standard
Signal
Name
Number
Defaults
1
PCR
Power Critical Alarm severity indicator
2
PMJ
Power Major Alarm severity indicator
3
PMN
Power Minor Alarm severity indicator
4
R1
BD - Battery on Discharge alarm
5
R2
VLV - Very Low Voltage alarm
6
R3
FAJ - External Fuse Major alarm
7
R4
ACF – single rectifier input (AC or DC) Fail alarm
8
R5
RFA - single Rectifier Fail alarm
9
R6
MRFA - multiple Rectifier Fail alarm
10
R7
HV - High Voltage shutdown alarm
Using optional ES771 Mid-String Voltage Modules?
No – Go to next section.
H5692448
49