GE Infinity M Series Installation Manual page 77

High capacity with horizontal distribution, 13 u system with galaxy pulsar plus controller, 22u system with galaxy millennium ii controller, initial/supplemental frame, 22u system with supplemental frame and galaxy millennium ii controller
Table of Contents

Advertisement

NE-M Installation Guide
Pulsar Controller Status
Millennium Controller
Display
Status Display
No Alarm, but
individual Shunt
Currents are
displayed at or
above their
maximum display
values (≥600A for
loads, ≥800A for
battery)
BD
AC
DC
green green green
Display green
850050111
Issue 03 August 2017
Rect/
Dist.
Conv
Module
LED
LEDs
Normal
Norm
green
green
green
Possible Problem(s)
One or both QS871A shunt
inputs is open-circuit.
Possible Solution(s)
1. Verify that the respective shunt has its green and yellow wire
connections attached used for the current measurements.
2. Verify the shunt connection to the QS871A is good by verifying
the green and yellow wire connections from the shunt follows
through to the 10-pin connector at the respective QS871A.
H5692448