GEH-6639 (Draft) GE Industrial Systems CS300 Half Controlled Power Supply for Inverter DC-Link User‘s Guide...
Page 2
This document shall not be reproduced in whole or in part nor shall its contents be disclosed to any third party without the written approval of GE Industrial Systems. CS300 is a trademark of General Electric Company. USA.
CS300 SAFETY SYMBOL LEGEND / LÉGENDE DES SIGNES DE SÉCURITÉ ARNING Commands attention to an operating procedure, practice, condition, or statement which, if not strictly observed, could result in personal injury or death. Attire l’attention sur les modes d’utilisation et les procédés et conditions d’exploitation qui, en cas d’inobservation, pourraient entraîner des blessures corporelles ou la mort.
CS300 TABLE OF CONTENTS SAFETY SYMBOL LEGEND / LÉGENDE DES SIGNES DE SÉCURITÉ ...... 3 CHAPTER 1 - SAFETY PRECAUTIONS ..............7 CHAPTER 2 - COMPONENT IDENTIFICATION AND SPECIFICATION ....11 2.1 GENERAL DESCRIPTION ..................... 11 2.2 POWER SUPPLY ........................11 2.3 DESCRIPTION OF POWER TERMINALS ................
CS300 Chapter 1 - SAFETY PRECAUTIONS The terms “Inverter”, “Controller” and “Drive” are sometimes used interchangably through- out the industry. We will use the term “Drive” in this document Les mots “Inverter”, “Controller” et “Drive” sont interchangeables dans le domaine industriel.
Page 8
GEH-6639 ! - FIRE AND EXPLOSION HAZARD / ATTENTION! – RISQUE D’INCENDIES ET D’EXPLOSIONS: ARNING Fires or explosions might result from mounting Drives in hazardous areas such as locations where flammable or combustible vapors or dusts are present. Drives should be installed away from hazardous areas, even if used with motors suitable for use in these locations.
Page 9
CS300 Protect the device from disallowed environmental conditions (temperature, humidity, shock etc.) The electrical commissioning should only be carried out by qualified personnel, who are also responsible for the provision of a suitable ground connection and a protected power supply feeder in accordance with the local and national regulations.
CS300 Chapter 2 - COMPONENT IDENTIFICATION AND SPECIFICATION 2.1 GENERAL DESCRIPTION CS300 is a half-controlled three phase AC/DC converter for supplying DC link voltage to a series of AC Drives, with C and D terminals parallel connected. The precharge of the drive capacitors (time setting set via dip-switches) is done by partializing the mains voltage via a thyristors bridge.
GEH-6639 2.4 DESCRIPTION OF CONTROL TERMINALS Terminals Function Voltage, Current Input of the precharge enable control (15 - 35V, 5 - 11mA) Output of the MLP static signal (low - active signal) (5 … 35V, 20mA source) (Common) Ground of the MLP and ML static signals Reference point for Power supply +24V Power supply output +24V (32V / 300mA max)
GEH-6639 2.6 CONVERTER SIZE SELECTION Within the specified voltage field, the CS300 converter supplies the same rated direct current independently of the voltage itself. The increase of the output voltage causes an increasing in the transferred power, whereas inverters are devices with a typically constant transferred power (the supplied current decreases with the increasing of the output voltage).
CS300 2.6.2 Drive DC Current (DC Link Circuit) AV300 -… Rated motor Motor Current Current Fuses Dclink I DClink I power efficiency DClink Continuous class 1 Overload class 2 Superfast class 1 class 2 [kW] 0,55 0,71 1,56 2,12 4003 4003 0,75 0,74...
GEH-6639 Chapter 3 - SELECTION OF THE CS300 CONVERTER The CS300 converter has to be chosen so that the sum of the inverter DC-link currents, both for class 1 and 2, is lower or equal to the corresponding ones stated in chapter 2.6.1. 3.1 DIP-SWITCHES AND JUMPER On R-SM3-L card S1.1-4...
Page 17
CS300 Having as a unit of measure the “L” inductance in Henry, the “C” capacitor in Farad and the “R” resistance in Ohm, according to the above mentioned data: = 1331.21 rad/S = 357.14 from which: = 0.00117 s from which: states the time needed by the current to reach its maximum value ) the peak current can be calculated with the following formula: = 572.3A...
GEH-6639 S1.1 S1.2 S1.3 S1.4 Delay in the thyristor disabling 1.1mS +/- 10% 2.2mS +/- 10% 3.3mS +/- 10% 4.4mS +/- 10% 5.5mS +/- 10% 6.6mS +/- 10% 7.7mS +/- 10% cs080 From the above table, considering the example, a delay of 1.1mS is selected by setting: S1.1 OFF - S1.2 ON - S1.3 ON - S1.4 OFF.
CS300 1) Set all the switches in off position (18-seconds ramp time), use a current probe able to detect a current peak 10mS between the C or D terminal of the DC-LINK. 2) At this point read the measuring of the maximum peak current present on the DC-LINK during the precharging phase.
GEH-6639 Chapter 4 - CONTROL DESCRIPTION 4.1 OK RELAY The OK relay has a normally open contact which close at the end of the precharging phase if no alarm condition is present (overtemperature, power supply on the regulation card +/-15V). The contact is closed during the normal functioning of the device and also during an undervoltage situation.
GEH-6639 Chapter 6 - CONVERTER OPERATION 6.1 EXAMPLE OF TERMINAL STRIP CONNECTION Note ! Fan with external supply only from 1050A size 2 4 6 PRECHARGE and higher COMMAND U V W Digital output From 1050 OK Relay size ——————— INSTRUCTION MANUAL ————————...
CS300 6.2 SIGNAL DIAGRAM AC CONTACTOR U.V.W PRECHARGE ENABLE DC-LINK VOLTAGE PRECHARGE TIME OK RELAY Figure A AC POWER SUPPLY. MLP signal TYRISTOR FIRING PRECHARGE ML signal " CV ON " ML signal "CV OFF " 150 ms MIN Figure B ———————...
GEH-6639 6.3 COMMON BUS MULTI-INVERTER SYSTEM DC BUS External fuses Braking unit CS300 Drive Drive Drive External braking AC mains resistor choke “Rbr” AC mains contactor OPTION External fuses AC MAINS INPUT * : Fuses for cables protection. ——————— INSTRUCTION MANUAL ————————...
Motors repairs on General Electric motors are gener- ally handled by GE Authorized Electric Motor Servicenters or GE Apparatus Service Shops. For spe- cific instructions on your motor, call the distributor from which it was purchased and be prepared to furnish complete nameplate data.
Page 27
CS300 Notes: ——————— Half controlled power supply for inverter DC-Link ————————...
Page 28
GE Industrial Systems General Electric Company GEH-6639 (Draft) + 1 540 387 7000 1501 Roanoke Blvd. 010119 www.GEindustrial.com Salem, VA 24153-6492 USA SIEI...