Install Converters; Install Battery Voltage Temp (Vt)-Probes; Install Aux Display (Ne830A) Alarm Cable (Optional); Table 8 Power Connections - Ne830 - GE Infinity M Series Installation Manual

High capacity with horizontal distribution, 13 u system with galaxy pulsar plus controller, 22u system with galaxy millennium ii controller, initial/supplemental frame, 22u system with supplemental frame and galaxy millennium ii controller
Table of Contents

Advertisement

NE-M Installation Guide

Install Converters

Repeat the above steps for converters; use converter-only slots first if provided. These are the lowest mounted shelves
and labeled "Converter Only".
For more information on rectifiers and converters, see the Troubleshooting section.

Install Battery Voltage Temp (VT)-Probes

QS873A VT Probes can be used with or without mid-string voltage monitoring. Only one probe is required to allow the
battery slope thermal compensation function to be utilized.
Refer to the Galaxy Pulsar Plus Family Product Manual for installation instructions.

Install Aux Display (NE830A) Alarm Cable (Optional)

The optional NE830 Aux Display, when ordered separately, will require field installation. To do so, perform the following
steps:
Step
No – go to Step1.
1
Connect and wire to field installed NE830A.
Install wiring per NEC and local rules for Class 3 circuits.
2
Note: Cable supplied with NE830A is suitable for Class 3 circuits.
Apply appropriate terminals (if necessary) to the cable after removing the supplied had 1/4 inch Faston ®
terminals:
Pin
Wire
1
Green
3
2
White
3
Red
4
Black
Connect and wire connection to NE830A. Alarm cable comcodes are
15ft: CC847922101, 150 ft.: CC848804765.
Table 9 Alarm Connections -
Pin
Wire
4
1
Black
2
Brown
3
Bare
850050111
Issue 03 August 2017
Is the NE830A factory installed?

Table 8 Power Connections - NE830

Signal Name
Connect to:
Earth Ground
Frame Ground
24V+/-
24V point to be monitored (+24V or -24V)
48V-
-48V point to be monitored (-48V only)
Common
Return for signals on pins 2 & 3
Return
NE830
Signal Name
Common
Open On Alarm
Close On Alarm
Figure
Action
Yes –no action required. Go to next section.
Alarm Cable
Connector
NE830 Alarm Cable Connector
H5692448
62