NE-M Installation Guide
Configure Controller – Minimum
This section covers the basic operations that must be performed so that the controller is minimally configured. See the
controller manual for further detail.
Configure Pulsar Controller
RS-232 Port
This display shows the front panel display for a system with both rectifiers and converters. The display (V1 versus V2)
correlates with test jacks. The large font indicates the "Primary" or rectifier dc bus; the smaller font shows the
"Secondary" or converter dc bus.
Menu Navigation Buttons
Parameter Change
Navigate
Enter Button
ESC Button
Configuration Attribute
Step
to Change
1
Date
2
Time
850050111
Issue 03 August 2017
Plant Status LEDs
Plant Voltage and
Voltage Test Jacks
Plant Mode
Figure 86 Front Panel - Pulsar Plus Controller
Increase or decrease the value of the selected parameter.
Navigate menus – move to different selected menu item.
Enter a sub-menu or confirms a parameter change.
Go to the Main Menu from the Normal display.
Go up one menu level or exits a parameter change without saving.
Configuration
Format
This field allows you to select one of the following date formats: MM/DD/YY,
DD/MM/YY, YY/MM/DD, MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD. Use the <+>
or <-> key to select the desired format and press <ENTER> to save the change.
Month
Use this field to change the month; the possible value is from 1 to 12.
Day
Use this field to change the day of the month; the possible value is from 1 to
31.
Year
Use this field to change the year; the possible value is from 1992 and up.
Note: The system will validate the entries before the system date is modified.
Load Current
Menu Navigation
Menu Path/Action - Pulsar
Shunt Monitors
System
Settings
H5692448
Date
Time
63