Commissioning; Operating Instructions; Protection Against Electrostatic Discharges - ABB TTH300 Operating Instructions Manual

Head-mount temperature transmitter
Hide thumbs Also See for TTH300:
Table of Contents

Advertisement

ATEX - Zone 1 (0)
Designation: II 2 (1) G Ex [ia] ib IIC T6 Gb (Ga)
Zone 0
Ex-area Zone 1
or 1
D
ia
ia
J
A
B
Fig. 3
A Sensor B Transmitter in the housing with IP rating IP 20
C separator [Ex ib] D interface for LCD display
When using the transmitter in Zone 1, it must be installed in a
suitable housing with IP rating IP20. The input for the supply
isolator must have an [Ex ib] design. When using the
transmitter in Zone 1, you must ensure that impermissible
electrostatic charging of the temperature transmitter is
prevented (observe the warnings on the device). As the user, it
is your responsibility to ensure that the sensor instrumentation
meets the requirements of applicable explosion protection
standards. The sensor can be installed in Zone 1 or Zone 0.
ATEX - Zone 1 (20)
Designation: II 2 G (1D) Ex [iaD] ib IIC T6 Gb (Da)
Zone 0, 1
Ex-area Zone 1
or 20
D
ia
ia
J
A
B
Fig. 4
A Sensor B Transmitter in the housing with IP rating IP 20
C separator [Ex ib] D interface for LCD display
When using the transmitter in Zone 1, it must be installed in a
suitable housing with IP rating IP20. The input for the supply
isolator must have an [Ex ib] design.
When using the transmitter in Zone 1, you must ensure that
impermissible electrostatic charging of the temperature
transmitter is prevented (observe the warnings on the device).
As the user, it is your responsibility to ensure that the sensor
instrumentation meets the requirements of applicable
explosion protection standards. The sensor can be installed in
Zone 0, Zone 1, or Zone 20.
ATEX - Zone 2
Designation: II 3 G Ex nA IIC T1-T6 Gc
Safe area
ib
C
Fig. 5
A11127
A Sensor B Transmitter in the housing with IP rating IP 54
C separator D interface for LCD display
When using the transmitter in Zone 2, observe the following:
— The temperature transmitter must be installed in its own
— External measures must be made for the power supply
— The electrical connections may only be opened or closed
— When using the transmitter in Zone 2, you must ensure
Safe area
2.5
ib
The commissioning and parameterization of the device may
ib
also be carried out in potentially explosive atmospheres using
a handheld terminal that has been approved accordingly under
consideration of an intrinsic safety installation check.
Alternatively, an Ex modem can be connected to the circuit
outside the potentially explosive atmosphere.
C
A11128
2.6
2.6.1
The plastic parts inside the device can store electrostatic
charges.
Make sure that no electrostatic charges can accumulate when
handling the device.
Ex-area Zone 2
D
J
A
B
housing. This housing must at least meet IP rating IP54 (in
accordance with EN 60529) and the other requirements of
the potentially explosive atmosphere (e. g. a certified
housing).
circuit in order to prevent the rated voltage from being
exceeded by more than 40% in the event of transient
disturbances.
when there is no hazardous atmosphere.
that impermissible electrostatic charging of the
temperature transmitter is prevented (observe the
warnings on the device).

Commissioning

Operating instructions

Protection against electrostatic discharges

Safe area
C
A11129