Factory Wired Options; P3-Drives Isolation Fuses - Eaton H-Max Series Manual

Drives intellipass/intellidisconnect frames 4-7
Hide thumbs Also See for H-Max Series:
Table of Contents

Advertisement

Factory Wired Options

The Intellpass and IntelliDisconnect can be supplied with serveral factory wired power options. The sections below describe
the options.
Options
HMAX Option Matrix
P3 - Drive Isolation Fuses
P6 - Drive Isolation Contactor includes manual switch
PE - Drive Output contactor
IS - Isolation Switch
SA - Space Heater (3R only)
K9 - Aux Contacts
M1 - Manual Bypass includes L4 and drive isolation contactor and door switch
L3 - H-Max Pilot Lights
L4 - H-Max Pilot Lights
P3- Drive Isolation Fuses
This option is available for both the IntelliPass and IntelliDisconnect designs 208/230V up to 30Hp and 480V models up to 75 hp.
3 Power Fuses are supplied wired to the Drive input. They are provided between the disconnect device and drive. The fuses
are not used in the bypass mode. The fuses are for drive protection only. They are listed, Class CC or Special Purpose Fuse
cube fuses sized according to the following table. This option cannot be used with IS Isolation switch or P6 isolation contac-
tor options. See IntelliDisconnnect or Typical IntelliPass schematic.
Hp Rating and Fuse Rating (A)
HP
208 V Fuse
1
6
2
12
3
20
5
25
7.5
30
10
45
15
60
20
80
25
90
30
100
40
N/A
50
N/A
60
N/A
75
N/A
230 V Fuse
460 V Fuse
6
5
12
6
20
8
25
12
30
20
45
25
60
30
80
45
90
45
100
50
N/A
60
N/A
80
N/A
90
N/A
100
H-Max Series Drives IntelliPass®/IntelliDisconnect® IL04008003E April 2013 www.eaton.com
IPass
IDisc
X
X
X
N/A
N/A
X
X
N/A
X
X
X
X
X
N/A
N/A
X
X
N/A
Factory Wired Options