Factory Wired Options
IS - Drive Isolation Switch
This option is available on the IntelliPass models only. This is an MMP or molded case switch, installed at the input of the
Drive to be used as a switch only to isolate the drive from input power. The IntelliPass door must be opened to operate this
switch – a thru the door operator is not supplied. The switch removes main power from the Drive. The Drive display and logic
will remain active because of the separate 24Volt power supply, but the drive will not run. The drive Keypad is still powered
and the bypass feature remains operational and the motor can be run in bypass using the keypad. This option cannot be used
with P3 or P6 options. See Typical IntelliPass Schematic.
12
H-Max Series Drives IntelliPass®/IntelliDisconnect® IL04008003E April 2013 www.eaton.com
Drive Isolation Switch Option IS
2
3
4
2 3
4