L3/L4-Hmax Pilot Lights - Eaton H-Max Series Manual

Drives intellipass/intellidisconnect frames 4-7
Hide thumbs Also See for H-Max Series:
Table of Contents

Advertisement

Factory Wired Options
L3/L4 - HMAX Pilot Lights
The L3 option is available only on the IntelliDisconnect models and provides 3 door mounted pilot lights, 1 red, 1 white and 1
green. The L4 option is available on the IntelliPass models and provides 4 door mounted pilot lights: 1 red, 1 white, 1 green
and 1 amber.
The white "Power On" light indicates that 24VDC power is active. However, Caution is advised if the light is not illuminated,
as this is may not be an indication that main power has been removed. If the light fails or the 24V power supply fails, main
power may still be present. Always follow proper safety procedures to determine the presence of main power on the unit
The red "Drive Fault" light indicates a Drive fault is present.
The green light indicates the system is commanded to run from the Drive and the Drive is in the "run" mode, the drive out-
put contactor is also energized if the PE option is supplied. The speed of the motor will depend on the Drive speed signal.
The motor may not be rotating if commanded at zero speed.
The amber light indicates the system has been commanded to run in bypass. The bypass contactor should be energized and
the motor running across the line.
16
H-Max Series Drives IntelliPass®/IntelliDisconnect® IL04008003E April 2013 www.eaton.com
®
H-Max
Series
TM
Intellipass
®
Active Energy Control
An Eaton Green Solution
L4 Option
L3 Option

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hmx01134nap3Hmx01131nais

Table of Contents