Replacing The Akm Board; Replacing The Rec10 Master - Riello Family KIS Series Installer And User Manual

Table of Contents

Advertisement

Available languages

Available languages

FAMILY CX
WHERE IS THE REC10 INSTALLED?
- select the type of boiler INSTANTANEOUS (the boiler is the combined
variety)
INSTANTANEOUS
SELECT THE PLANT CONFIGURATION
- select the type of domestic hot water request on the FLOW METER.
FLUSSIMETRO
FLUSSOSTATO
- Once the guided procedure has finished, the REC10 will go to the initial
screen.
Continue with the configuration as follows:
- access the technical parameters as explained in the section" Accessing
the technical parameters" entering the SERVICE password
- select PARAMETERS with the "UP" and "DOWN" keys, confirming the
selection
- next change the following parameters:
ENABLE FILLING: set to 1.
Then proceed with the reprogramming of the boiler, carrying out the
operations described in the section "Programming the boiler".

5.21 Replacing the REC10 Master

b
The system configuration operations need to be carried out by
professionally qualified personnel of the Technical Assistance Centre.
When replacing the REC10 MASTER, at the subsequent restart it displays
an initial screen with the firmware revision.
Pressing "ENTER" starts a guided procedure for configuring the system,
see the section "Configuring the system".
Follow the procedure and carry out the DA AKM type of confi guration.
30
BOILER
ON BOARD
AMBIENT
PLANT
CH ONLY
HW TANK
IMPIANTO
REC10R
Welcome at home
PRESS ANY KEY TO
SELECT THE TYPE OF

5.22 Replacing the AKM board

The system configuration operations need to be carried out by professionally
qualified personnel of the Technical Assistance Centre.
The systems continually carries out a consistency control between the
configuration data saved on the AKM electronic board and that saved in the
REC; therefore, when replacing the AKM electronic board, it might happen
that the system detects an inconsistency between the data saved on the AKM
and that in the REC.
In this case, the latter will ask the user which of the two configurations is to
be considered valid; selecting to recuperate the configuration from the REC
itself it is possible to avoid reconfiguring the machine:
- select REC 10 with the "UP" and "DOWN" keys, confirming the selection.
SELECT THE TYPE OF
R02.06
CONTINUE
CONFIGURATION
FROM AKM
NEW
CONFIGURATION
FROM AKM
REC10