EN - INSTALLER AND USER MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Riello KIS Series

  • Page 1 Family KIS EN - INSTALLER AND USER MANUAL...
  • Page 2 FAMILY Family boiler complies with basic requirements of the following Directives: In some parts of the booklet, some symbols are used: - Regulation (EU) 2016/426; WARNING = for actions requiring special care and adequate preparation. - Efficiency directive: Article 7(2) and Annex III of directive 92/42/EEC - Electromagnetic compatibility directive 2014/30/EU - Low-voltage directive 2014/35/EU PROHIBITED = for actions THAT MUST NOT be performed. - Directive 2009/125/EC Ecodesign for energy-using appliances Section destined for user also. - Regulation (EU) 2017/1369 Energy labeling - Delegated Regulation (EU) No. 811/2013 - Delegated Regulation (EU) No. 813/2013. Warning This instructions manual contains data and information for both the user and the installer. Installer’s-user’s manual 3-21 Specifically, note that the user, for the use of the appliance, must refer to chapters: Boiler operating elements - Warnings and safety •...
  • Page 3: Warnings And Safety

    ENGLISH ENGLISH It is forbidden to disperse the packaging material in the environment and leave it within children's reach as it may be a potential source of danger. It must be disposed WARNINGS AND SAFETY in accordance with the present law. It is forbidden to obstruct the condensate drain outlet.
  • Page 4: Minimum Distances

    FAMILY ANTI-FREEZE SYSTEM The boiler is fitted as standard with an automatic anti-freeze system that activates when the temperature of the water in the primary circuit falls below 5°C. This system is always active and provides protection for the boiler up to an air temperature in the installation area of >0°C. To take advantage of this protection (based on burner operation), the boiler must be able to switch itself on;...
  • Page 5: Gas Connection

    The boiler is supplied without the flue gas exhaust/air suction kit, since it is possible The minimum calibration should not be modified. to use the accessories for condensing appliances that best fit the installation characteristics (see RIELLO catalogue). The maximum lengths of the pipes refer to the flue accessories available in the RIELLO catalogue.
  • Page 6 FAMILY Table of adjustments INSIDE CHIMNEY PIPES Make sure that the air intake and exhaust pipes of the combustion products are watertight. WARNINGS: twin flue pipe The appliances connected to a collective pipe must all be of the same type and have Fan rotations rpm Pipes Ø50 Pipes Ø60...
  • Page 7: Draining The Heating System

    ENGLISH Filling the heating system and eliminating air max water level (limit) Note: even if the boiler is fitted with a semi-automatic filling device, the first filling operation must be carried out by turning the filler tap (B) with the boiler OFF. Note: each time the boiler is powered up, the automatic venting cycle is carried out.
  • Page 8 FAMILY CONTROL PANEL (REC10CH) Boiler control panel REC10CH Confirm PLANT 09/04/2021 12:17 back= return to the previous screen MENU STATE cancel selection return to the main screen (press > 2 sec.) °C INFO - From the main screen they allow you to choose between the HOT WATER TEMPERATURE options: MENU, INFO, SET, STATE, PLANT.
  • Page 9 ENGLISH Structure of the MENU tree of the REC10CH DEFAULT VALUE FACTORY MINIMUM MAXIMUM ACCESS LEVEL VALUE VALUE NOTES VALUE MENU SETTINGS USER TIME & DATE USER DAYLIGHT SAVINGS TIME FUNCTION ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE USER LANGUAGE ENGLISH / ITALIANO / ... USER BACKLIGHT 5 min...
  • Page 10 FAMILY DEFAULT VALUE FACTORY MINIMUM MAXIMUM ACCESS LEVEL VALUE VALUE NOTES VALUE MENU DECR COOLING SP 0°C 0°C 10°C SERVICE PUMP DUTY CYCLE INSTALLER RESET CH TIMERS FUNCTION NOT ACTIVE FUNCTION NOT ACTIVE FUNCTION ACTIVE INSTALLER INSTALLER: only in DHW THERMOSTAT RELATED RELATED ABSOLUTE...
  • Page 11 ENGLISH DEFAULT VALUE FACTORY MINIMUM MAXIMUM ACCESS LEVEL VALUE VALUE NOTES VALUE MENU EXHAUST PROBE RESET INSTALLER INSTALLER: only if instantaneous ADD WATER TANK and “only heating” confi g. INSTALLER WATER TANK REMOVE WATER TANK INSTALLER INSTALLER: only if HP enable 50°C 37.5°C 60°C...
  • Page 12 FAMILY DEFAULT VALUE FACTORY MINIMUM MAXIMUM ACCESS LEVEL VALUE VALUE NOTES VALUE MENU BOOSTER DELAY 30min 1 min 60 min INSTALLER BOOSTER DELTA TEMP 5°C 1°C 20°C INSTALLER INSTALLER OAT SENSOR TYP MINIMUM PUMP SPEED 100% INSTALLER MAXIMUM PUMP SPEED 100% 100% INSTALLER...
  • Page 13 ENGLISH 4.2.2 Configuration of the zone - Choose between the options suggested and confirm your choice. It is possible to customise the management of the heating zone by accessing the ZONES PARAMETERS MANAGER menu. - Access to menu TECHNICAL INSTALLATION ZONES MANAGER ANTI-CYCLE FUNCTION MODIFY ZONE.
  • Page 14 FAMILY RIDUZIONE NOTTURNA PARALLELA Using the REC10CH it is possible to set the value of the following parameters: BUILDING TYPE: it is an indication of the frequency with which the value of the calculated outdoor temperature for thermoregulation is updated, a low value will be used for buildings that have little insulation.
  • Page 15 ENGLISH The boiler will be in function until the selected temperature is reached, afterwards it will WINTER : select STATE BOILER HEATING AND HOT WATER be in “standby” again keeping the outlet temperature displayed. If faults arise in ignition or (WINTER) to activate heating and domestic hot water functions.
  • Page 16 FAMILY IMPORTANT: The chimney sweep function is active for a time limit of 15 minutes; the TECHNICAL COMBUSTION ANALYSIS burner shuts down if an outlet temperature of 95° C is reached. It will ignite again when the PARAMETERS temperature falls below 75° C. WEATHER COMPENSATION In the case of a low temperature system we recommend carrying out the efficiency RANGE RATED...
  • Page 17 ENGLISH Only for installer: At the end of the procedure, proceed with the automatic vent cycle as TECHNICAL described in “Filling the heating system and eliminating air”. WEATHER COMPENSATION THE PARAMETER WILL BE CHANGED RANGE RATED CALIBRATION COMBUSTION ANALYSIS CONFIRM CANCEL EXHAUST PROBE RESET INSTALLER...
  • Page 18 FAMILY 4.15 Error history - select LANGUAGE: ENGLISH - setting TIME and DATE The ERROR HISTORY function is automatically enabled only after the machine has been powered up for at least 2 consecutive hours, during this period of time any alarms that arise TIME &...
  • Page 19: Boiler Type

    ENGLISH 4.22 Replacing the MAIN PCB board COMBUSTION SELF-CALIBRATION Function used by the after sales service to make an automatic combustion bend correction if The system configuration operations need to be carried out by professionally qualified the CO values (shown in the technical data) are outside the permitted range. personnel of the Technical Assistance Centre.
  • Page 20 FAMILY - To close the fixing nuts of the air/gas conveyor assembly, use a tightening torque of - Clean the parts of the siphon from any solid residues. 8 Nm. - Turn the power and gas feeding to the boiler back on. Do not remove the safety shutter and its sealing gasket as their presence is in- tended to prevent the escape of burnt gases into the environment in the event of If there are obstinate combustion products on the surface of the heat exchanger,...
  • Page 21: User Functions

    ENGLISH USER Depending on the type of application, some of the functions described in this manual might not be available. USER FUNCTIONS PLANT 09/04/2021 12:17 MENU STATE °C INFO HOT WATER TEMPERATURE 1 MENU DEFAULT VALUE FACTORY MINIMUM MAXIMUM ACCESS LEVEL VALUE VALUE NOTES...
  • Page 22: Start Screen

    FAMILY START SCREEN 8.2.1 If ON is selected, the zone requests are met. Upon ignition, the REC10CH might: - request the setting of the time and date (see “11.1 Settings”) 8.2.2 AUTO - display the firmware version and require a button to be pressed in order to continue. If AUTO is selected, the zone requests will be managed based on a scheduled programme.
  • Page 23 ENGLISH 10 INFO The INFO function can be used to display a series of data regarding the system. HOT WATER ATTENTION - The displayed data cannot be modified. THE PARAMETER WILL BE CHANGED SCREED HEATER OPERATING HOURS ZONE 2 SET-POINT 58,0 °C DELIVERY PROBE...
  • Page 24: Time Schedule

    FAMILY 11.1.5 Time schedule Select the desired time band. - Select MENU TIME SCHEDULE (only if the time schedule is enabled MAIN MAIN (if POR=1) or ZONE 1 (if POR=1) or ZONE 2 (if POR=1) or HP DHW. START THURSDAY 07:30 08:30 NOTES...
  • Page 25 ENGLISH The day will be highlighted and others can be selected using the same procedure The user will once again be prompted to confirm the selections made. CONFIRM COMFORT mode temperature and duration programming can be abandoned at any time MAIN by pressing BACK.
  • Page 26: Technical Data

    FAMILY 14 TECHNICAL DATA FAMILY DESCRIPTION 25 KIS 30 KIS 35 KIS Rated heat input kW-kcal/h 20,00 (****)-17.200 25,00-21.500 32,00-27.520 Nominal heat output (80°/60°) kW-kcal/h 19,50-16.770 24,43-21.006 31,23-26.860 Nominal heat output (50°/30°) kW-kcal/h 21,32-18.335 26,88-23.113 34,37-29.556 Reduced heat input kW-kcal/h 3,60-3.096 5,00-4.300 4,90-4.214...
  • Page 27 ENGLISH FAMILY PARAMETERS Lower Wobbe index (at 15°C-1013 mbar) MJ/m³S 45,67x 70,69 Net Calorific Value MJ/m³S 34,02 Supply nominal pressure mbar (mm H2O) 20 (203,9) 37 (377,3) Supply minimum pressure mbar (mm H2O) 10 (102,0) 25 KIS 30 KIS 35 KIS PARAMETERS Burner: diameter/length 70/86...
  • Page 28 FAMILY GENERAL SECTION 25 KIS 30 - 35 KIS 15.1 [EN] - Boiler operating elements Main heat exchanger Non-return valve Three-way valve (stepper) Filling tap Drain valve Flame detection electrode/Ionisation DHW heat exchanger sensor Mixer Filling solenoid DHW NTC probe Burner Return NTC probe Water gauge...
  • Page 29 FAMILY [EN] - Residual head of circulator (e.g. booster circulator)) is only active in the it is necessary to make the most of the 4 - EXCEPTIONAL USE OF A STANDARD heating function. The circulator always oper- boiler discharge head in order to ensure NON-SPEED ADJUSTABLE CIRCULA- The boiler is equipped with a high efficiency TOR (PUMP DUTY CYCLE = 0): mode...
  • Page 30 FAMILY TSC2 C.S.A. blu (-) F=3.15A F marrone (+) V Hv marrone rosa arancione E.R. arancione (SE) X3 X7 arancione (SE) rosa (OT+) nero (-) rosa (OT+) nero (TA) arancione (A) F1=4A T giallo (B) nero (TA) rosso (+24 Vdc) bianco (TBT) bianco (TBT) AKM0x...
  • Page 31 FAMILY 15.8 [EN] Fumes exhaust configuration B23P-B53P Ø60-100 Ø80-125 Ø80-80 15.9 [EN] MAX LENGTH PIPES Ø 80 flue gas pipe length (m) air suction pipe length (m) Lunghezza tubo aspirazione aria (m) Maximum straight length (m) Pressure drop (m) Diameter Hole in wall bend Type of duct...
  • Page 32 FAMILY Boiler control panel EN - REC10 ENTER Confirm PLANT - Return to the previous page/cancel selection 09/04/2021 12:17 BACK MENU STATE - Return to the main screen (press > 2 sec.) - From the main screen they allow you to choose between °C the options: MENU, INFO, SET, STATE, PLANT.
  • Page 33 ✎...
  • Page 34 ✎...