Reset Function - Riello Family KIS Series Installer And User Manual

Table of Contents

Advertisement

Available languages

Available languages

For fault E041
If the pressure drops below the safety threshold of 0.3 bar the boiler displays
the fault code "E041 - WATER TRANSDUCER PRESS OK TO FILL THE
SYSTEM" for a transitional time of 10 min during which it is possible to
start the semi-automatic loading procedure, pressing the "ok" key to fi ll
the system (the procedure can only be started in SUMMER or WINTER).
WATER TRANSDUCER
PRESS OK FILL THE SYSTEM
During the loading phase the scrolling message "SEMI-AUTOMATIC
FILLING IN PROGRESS" is displayed at the foot of the screen, while the
pressure highlighted on the display should start to rise.
When the loading is fi nished the scrolling message "SEMI-AUTOMATIC
FILLING FINISHED" is displayed at the foot of the page.
When the transitional time has fi nished, if the fault persists the fault code
E040 is displayed.
When the boiler has fault E040 manual loading should be carried out using
the fi ller tap (A) until the pressure is between 1 and 1.5 bar.
b
If the pressure drops frequently, contact the Technical Assistance
Centre.
A
For fault E091
The boiler has an auto-diagnostic system which, based on the total number
of hours in certain operating conditions, can signal the need to clean the
primary heat exchanger.
The intervention of the Technical Assistance Centre is necessary.
E041

14.1 Reset function

In order to reset the boiler's operation in the event of a fault, it is necessary
to access the fault description screen. If the lockout is of a non-volatile type
that requires a reset procedure, this will be indicated on the screen, and can
be carried out by pressing the "ok" button on the REC10.
LIMIT THERMOSTAT
PRESS OK TO RESET
At this point, if the correct operating conditions have been restored, the
boiler will restart automatically.
If the attempts to reset the fault do not restore the boiler's functionality,
please contact your local Customer Support Service.
Up to a maximum of 3 reset attempts can be made using the REC10, after
which the machine must be disconnected from the power supply to reset
the number of attempts available.
b
Request the intervention of the Technical Assistance Centre.
LIMIT THERMOSTAT
RESET ATT. EXHAUSTED
E020
E020
ENGLISH
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Family 25 kisFamily 30 kisFamily 35 kis

Table of Contents