ProFire PF2200-SB Product Manual page 85

Single burner controller
Hide thumbs Also See for PF2200-SB:
Table of Contents

Advertisement

#
Description
117
Reserved
118
Reserved
119
Digital Input ADC Start Fault
120
Digital Input ADC Read Fault
121
Digital Input ADC Stop Fault
122
Safety Output Mismatch
123
Processor Reset
124
Calibration CRC Failed
Brownout Reset Voltage
125
Incorrect
126
Flame 1 DC Input Open
127
Flame 2 DC Input Open
128
Factory Calibration Error
Process Setpoint Adjust Unit
129
Configuration Error
This fault can occur in one of two scenarios: a negative voltage is present on the Signal In terminal OR the BMS card has been compromised
[1]
[2]
This fault usually occurs when the BMS card has been compromised
Alarm Condition
BMS Card fault associated with internal ADC.
BMS Card fault associated with internal ADC.
BMS Card fault associated with internal ADC.
The primary and secondary processors of the BMS card disagree on the state of the
Safety Outputs.
Primary and/or secondary processor(s) of the BMS have reset due to a lock-up.
Periodic Calibration CRC check has failed
BMS card has been programmed with the incorrect brownout reset voltage.
BMS card internal circuit fault associated with Pilot 1 flame input.
BMS card internal circuit fault associated with Pilot 2 flame input.
BMS card calibration descriptor error.
Process Setpoint Adjust Input units are not valid (i.e. not set to a valid Temperature
Unit)
Section 6: APPENDIX A: ALARM CODES & RESPONSE TIMES
[2]
[2]
[2]
[2]
[2]
[2]
V 4.0
Set Time
2s
2s
2s
2s
0
0
0
[2]
2s
2s
0
0
Page 85 of 85