ProFire PF2200-SB Product Manual page 82

Single burner controller
Hide thumbs Also See for PF2200-SB:
Table of Contents

Advertisement

#
Description
26
Bath High Temp ESD
27
Bath Temp Mismatch
Bath Temp Configuration
28
Range Error
29
Bath 1 Sensor Open
30
Bath 1 Sensor Short
31
Bath 1 Out of Range
32
Bath 1 Stale Data
33
Bath 2 Sensor Open
34
Bath 2 Sensor Short
35
Bath 2 Out of Range
36
Bath 2 Stale Data
37
Outlet High Temp ESD
Outlet Temp Configuration
38
Range Error
39
Outlet Sensor Open
40
Outlet Sensor Short
41
Outlet Out of Range
42
Outlet Stale Data
43
Stack High Temp ESD
Alarm Condition
Bath Temperature Input is greater than High Temp ESD setpoint
Bath Temperature Input 1 does not match Bath Temperature Input 2
Bath Temperature Input settings are configured incorrectly with respect to one
another, mainly:
Pilot Off setpoint less than Main Off Or Process setpoints
OR
High Temp setpoint less than Main Off OR Pilot Off OR Process setpoints
OR
Low Temp setpoint greater than Process Setpoint
OR
High Temp out of range
Bath Temperature Input 1 sensor has an open circuit
Bath Temperature Input 1 in RTD Mode:
Input is measuring a short circuit
Bath Temperature Input 1 in Thermocouple Mode:
This alarm cannot be set
Bath Temperature Input 1 in RTD Mode:
Input is measuring outside of the valid range for RTD
Bath Temperature Input 1 in Thermocouple Mode:
Input is measuring outside of the valid range for Thermocouple
Bath Temperature Input 1 is not reading valid data
Bath Temperature Input 2 sensor has an open circuit
Bath Temperature Input 2 in RTD Mode:
Input is measuring a short circuit
Bath Temperature Input 2 in Thermocouple Mode:
This alarm cannot be set
Bath Temperature Input 2 in RTD Mode:
Input is measuring outside of the valid range for RTD
Bath Temperature Input 2 in Thermocouple Mode:
Input is measuring outside of the valid range for Thermocouple
Bath Temperature Input 2 is not reading valid data
Outlet Temperature Input is greater than High Temp ESD setpoint
Outlet Temperature Input settings are configured incorrectly with respect to one
another, mainly:
Pilot Off setpoint less than Main Off Or Process setpoints
OR
High Temp setpoint less than Main Off OR Pilot Off OR Process setpoints
OR
Low Temp setpoint greater than Process Setpoint
OR
High Temp out of range
Outlet Temperature Input sensor has an open circuit
Outlet Temperature Input in RTD Mode:
Input is measuring a short circuit
Outlet Temperature Input in Thermocouple Mode:
This alarm cannot be set
Outlet Temperature Input in RTD Mode:
Input is measuring outside of the valid range for RTD
Outlet Temperature Input in Thermocouple Mode:
Input is measuring outside of the valid range for Thermocouple
Outlet Temperature Input is not reading valid data
Stack Temperature Input is greater than High Temp ESD setpoint
Section 6: APPENDIX A: ALARM CODES & RESPONSE TIMES
V 4.0
Set Time
2s
2s
0
6s
6s
6s
6s
6s
6s
6s
6s
2s
0
6s
6s
6s
6s
2s
Page 82 of 85