Description
16
Aux In 1 Out of Range
17
Aux In 1 Low Trip
18
Aux In 1 High Trip
19
Aux In 1 Configuration Error
20
Aux In 2 Contact Open
21
Aux In 2 Out of Range
22
Aux In 2 Low Trip
23
Aux In 2 High Trip
24
Aux In 2 Configuration Error
Process Setpoint Adjust
25
Configuration Error
Alarm Condition
Aux In 1 Input In 4-20 mode:
•
Input is less than 3 mA OR
Input is greater than 21 mA
•
Aux In 1 Input In Digital mode:
Input is not within a valid range
•
Aux In 1 Input In 4-20 mode:
•
Input is less than Aux In 1 Low Trip setting
Aux In 1 Input In Digital mode:
This alarm cannot be set
•
Aux In 1 Input In 4-20 mode:
Input is greater than Aux In 1 High Trip setting
•
Aux In 1 Input In Digital mode:
•
This alarm cannot be set
Aux In 1 Input In 4-20 mode:
Firing Rate Enable is Disabled AND Input High Trip less than Input Low Trip
•
plus Input Deadband
OR
•
Firing Rate Enable is Enabled AND Process Control Mode is not set to Staged
Heating
OR
•
Input Span Max less than Input Span Min
OR
Input High Trip greater than Input Span Max
•
OR
Input Low Trip less than Input Span Min
•
Aux In 1 Input In Digital mode:
Firing Rate Enable is Enabled
•
Aux In 2 input in 4-20 mode:
•
This alarm cannot be set
Aux In 2 input in Digital mode:
Input is open
•
Aux In 2 Input In 4-20 mode:
•
Input is less than 3 mA OR
Input is greater than 21 mA
•
Aux In 2 Input In Digital mode:
Input is not within a valid range
•
Aux In 2 Input In 4-20 mode:
•
Input is less than Aux In 2 Low Trip setting
Aux In 2 Input In Digital mode:
This alarm cannot be set
•
Aux In 2 Input In 4-20 mode:
Input is greater than Aux In 2 High Trip setting
•
Aux In 2 Input In Digital mode:
•
This alarm cannot be set
Aux In 2 Input In 4-20 mode:
Process Setpoint Adjust is Disabled AND Input High Trip less than Input Low
•
Trip plus Input Deadband
OR
•
Input Span Max less than Input Span Min
OR
Input High Trip greater than Input Span Max
•
OR
Input Low Trip less than Input Span Min
•
Aux In 2 Input In Digital mode:
•
Process Setpoint Adjust is Enabled
Process Setpoint Adjust is using a temperature that is not set up for Process Control.
Section 6: APPENDIX A: ALARM CODES & RESPONSE TIMES
[1]
[1]
V 4.0
Set Time
1s
2s
2s
0
2s
1s
2s
2s
0
0