2.1.2.9
LEVEL INPUT
The Level input (terminals 41-42) is meant to monitor an external level or flow measurement and
provide the necessary feedback in the event of a high and/or low level/flow event. Configurable as
disabled, digital input or 4-20mA signal through the user interface; the level input can be connected to
either a switch or transmitter.
In digital mode the level input can be used a wait, warning or an alarm when the contact opens. This
can be connected to a low or high trip switch depending on the application.
In 4-20mA mode the level input is used in conjunction with the low-trip and high-trip modes. These
modes are independent of one another and can be configured as either a wait, warning, or an alarm.
This input is intended to be connected to a level transmitter.
The following table outlines the behavior of the Level Input:
Input Configuration
Disabled
Digital Input
4-20mA
Event
Any
De-energized with digital mode set to wait
De-energized with digital mode set to warning
De-energized with digital mode set to alarm
Energized
Out of range
Low trip with low trip mode set to wait
Low trip with low trip mode set to warning
Low trip with low trip mode set to alarm
Active range
High trip with high trip mode set to wait
High trip with high trip mode set to warning
High trip with high trip mode set to alarm
Section 2: PF2200-SB PRODUCT DESCRIPTION
V 4.0
System Behavior
No Effect
Wait
Warning
Alarm
Run
Alarm
Wait
Warning
Alarm
Run
Wait
Warning
Alarm