V 4.0
4.3.4.7
BACKUP & RESTORE SETTINGS
BMS settings may be saved to a USB backup. This will create a
human readable .csv file that may be restored on the same unit later
or used to configure other units to the same settings.
Settings can only be restored to another single burner BMS unit,
settings are not compatible between Profire product lineups.
Settings can be restored between different firmware version,
however there is no guarantee of compatibility.
Not all settings may be restored due to mismatches in settings
between different firmware versions.
In these cases, the settings that have failed to restore are listed on
the UI screen. The commission date is always reset to default during
the restore. The operator must validate all setting on the BMS unit
and acknowledge by setting the new commission date.
Section 4: OPERATIONS and MAINTENANCE
Page 70 of 85