2.1.1 USER INTERFACE CARD

The User Interface Card allows interaction with the system through the use of the keypad and a display.
This card interacts with the BMS card through a proprietary communication protocol, called PFN, which
utilizes the RS-485 physical transport layer. PFN and power to the User Interface are factory wired to
the BMS card through a wiring harness.
2.1.1.1
MODBUS
Remote access to status information and non-safety critical settings can be achieved via the Modbus
port of the User Interface card. The Modbus port supports Modbus RTU over the RS-485 physical layer.
For a complete register list, see PF2200 Single Burner BMS – Modbus Registers. By design, safety critical
settings are not accessible via Modbus.
2.1.1.2
USB
The USB port of the User Interface Card has two main uses: data-logging and updating firmware. Data-
logging is enabled by going to the Firmware Update screen on the User Interface and is limited by the
size of USB stick-- a USB stick of size 1GB or larger is recommended. Firmware update is only
supported using authorized firmware bundles. Contact Profire Energy for an authorized firmware
bundle.
2.1.1.3
STATUS LED
The User Interface Card has a Status LED which is visible on the front panel of the product. Capable of
producing Red, Green and Amber colors, the states of the Status LED are defined below:
State
System is not running and is in lockout
System is not running and has an alarm
System is not running
System is running – no warnings or waits present
System is running – in wait state
System is running – in wait state with a warning present
System is running – with a warning present
LED Behavior
Fast Blink Red
Blink Red
Solid Red
Solid Green
Blink Green
Blink Amber
Solid Amber
Section 2: PF2200-SB PRODUCT DESCRIPTION