ProFire PF2200-SB Product Manual page 83

Single burner controller
Hide thumbs Also See for PF2200-SB:
Table of Contents

Advertisement

#
Description
Stack Temp Configuration
44
Range Error
45
Stack Sensor Open
46
Stack Sensor Short
47
Stack Out of Range
48
Stack Stale Data
49
Aux High Temp ESD
50
Aux Temp Out of Range
Aux Temp Configuration
51
Range Error
52
Ambient Temp Mismatch
53
Ambient Temp 1 Invalid
54
Ambient Temp 2 Invalid
55
No Process Temp
56
Pilot 1 Flame Fail
57
Pilot 2 Flame Fail
Pilot 1 Flame Detected While
58
Off
Pilot 2 Flame Detected While
59
Off
Flame 1 Load Monitor Check
60
Failure
Flame 2 Load Monitor Check
61
Failure
62
Pilot ADC Start Fault
63
Pilot ADC Read Fault
64
Pilot ADC Stop Fault
65
Flame 1 Voltage Fault
66
Flame 2 Voltage Fault
67
Low Voltage
68
High Voltage
69
System ADC Start Fault
70
System ADC Read Fault
71
System ADC Stop Fault
Alarm Condition
Stack Temperature Input settings are configured incorrectly with respect to sensor
type, mainly:
Pilot Off less than Main Off
OR
High Temp Less than Main Off
OR
High Temp Less than Pilot Off
Stack Temperature Input sensor has an open circuit
Stack Temperature Input in RTD Mode:
Input is measuring a short circuit
Stack Temperature Input in Thermocouple Mode:
This alarm cannot be set
Stack Temperature Input in RTD Mode:
Input is measuring outside of the valid range for RTD
Stack Temperature Input in Thermocouple Mode:
Input is measuring outside of the valid range for Thermocouple
Stack Temperature Input is not reading valid data
Aux Temp Input is greater than High Temp ESD setpoint
Aux Temp Input:
Less than 3 mA OR
Greater than 21 mA
Aux Temp Input settings are configured incorrectly with respect to one another,
mainly
Pilot Off less than Main Off
OR
High Temp Less than Main Off
OR
High Temp Less than Pilot Off
Ambient Temperature Measurement mismatch between sensors.
Ambient Temperature sensor 1 on BMS card is reporting an invalid reading.
Ambient Temperature sensor 2 on BMS card is reporting an invalid reading.
None of Bath, Outlet, or Aux temp are configured to be in Process Control mode
Pilot 1 has lost flame and/or failed to re-light
Pilot 2 has lost flame and/or failed to re-light
Flame has been detected on Pilot 1 input before Ignition
Flame has been detected on Pilot 2 input before Ignition
AC voltage on Pilot 1 input too low to reliably detect flame.
Note: Usually caused by loading of the flame rod to ground.
AC voltage on Pilot 2 input too low to reliably detect flame.
Note: Usually caused by loading of the flame rod to ground.
BMS Card fault associated with internal ADC.
BMS Card fault associated with internal ADC.
BMS Card fault associated with internal ADC.
Pilot Flame 1 flame test failure.
Pilot Flame 2 flame test failure.
System Voltage Input is less than Low Voltage Threshold:
In 12V Mode: 9.6V
In 24V Mode: 19.2V
System Voltage Input is greater than High Voltage Threshold:
In 12V Mode: 16.8V
In 24V Mode: 33.6V
BMS Card fault associated with internal ADC.
BMS Card fault associated with internal ADC.
BMS Card fault associated with internal ADC.
Section 6: APPENDIX A: ALARM CODES & RESPONSE TIMES
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
V 4.0
Set Time
0
6s
6s
6s
6s
2s
1s
0
6s
[2]
6s
6s
0
0
0
0
0
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
2s
Page 83 of 85