Important Safety Information; General Warnings - ProFire PF2200-SB Product Manual

Single burner controller
Hide thumbs Also See for PF2200-SB:
Table of Contents

Advertisement

I/O Type
Terminals
Power Out
Communication
Power In
28-32 (Power)
* The Bath Temperature Input is safety rated ONLY if the input is configured as a Dual. If configured as a Single
element the Bath temperature input is NOT safety rated. In order to enable a single element for the Bath
temperature, the user will be prompted with a disclaimer.
3.2

IMPORTANT SAFETY INFORMATION

All PF2200 installations must be field inspected by the Authority Having Jurisdiction to ensure proper
compliance to local electrical and gas codes. In addition, before installing the PF2200 please review the
following list of warnings. Failure to observe the following may result in death, electrocution, property
damage, product damage, and/or government fines.

3.2.1 GENERAL WARNINGS

Installation and product use must conform to the directions in this manual.
Solenoid powered outputs are rated to 5A max individually, however the power input to the BMS
card is fused at 10A. Care must be taken as to not exceed the 10A max input when using high-
powered solenoids.
Do not jumper solenoid (-) terminals together under any circumstance, this will compromise the
safety-integrity of the system.
Safety Functions must be end-to-end proven during commissioning (e.g. when using a high
pressure switch, ensure a high-pressure event presents a lock-out).
Safety
Rated
1&4 (UI)
No
2&3 (PFN)
No
No
Electrical Rating
7 – 35 VDC
500 mA Max
-7V to 7V Common Mode Range
12-24VDC
10A Max
Section 3: INSTALLATION and COMMISSIONING
V 4.0
Wire
Gauge /
Torque
14-30
AWG
0.22-0.25
Nm
14-30
AWG
0.22-0.25
Nm
12-30
AWG
0.5-0.6 Nm
Page 46 of 85