6.2. Power-up

It is mandatory to perform the tasks indicated in this point with the equipment sealed, thereby
avoiding any possible contact with live parts.
Once you have made a general visual inspection, checked the wiring between the equipment and ensured that the
equipment is sealed correctly, you can the proceed to power up the system. To do so:
1.
Power up the Ingecon
2.
Press the ON/OFF button so that the LED lights up.

7. Preventive maintenance

Unless indicated to the contrary, the recommended preventive maintenance tasks should be performed on an annual
basis.

7.1. Maintenance tasks

The various maintenance operations should be performed by qualified personnel. There is an elec-
trical discharge hazard.
To access the various compartments, account should be taken of the safety recommendations set out
in chapter "4. Safety instructions".
All the maintenance checks set out herein must be performed with the entire machine shutdown, in
safe manipulation conditions, including those specified by the customer for this type of operation.
The condition of the enclosure
A visual inspection should be made of the condition of the enclosure, checking the condition of the seals and covers. A
check should also be made to ensure that the equipment is firmly secured to the wall. Likewise, the enclosure should
also be checked for knocks or scratches that could degrade the equipment or lower its Protection Rating. Should any
defects of this nature be observed, then the parts affected should either be repaired or replaced.
Check that there is no moisture in the enclosure interior. If moisture is present, then the enclosure should be dried
out before the electrical connections are made.
Check that the enclosure components are firmly secured to their appropriate anchors.
Condition of the cables and terminals
Check that the cables run correctly so that there is no contact with live parts.
Check the insulation for damage and hot points, inspecting the colour of the insulation and terminals.
Visually check that the connections are firmly secured.
Ventilation
Clean the heat sink vanes and the ventilation grids.
Surrounding area
Check the characteristics of the surroundings to ensure that the buzzing noise is not amplified or transmitted.
32
μWind Interface through the auxiliary power supply input.
®