Analog Inputs - Ingeteam Ingecon mWind Interface Installation Manual

Table of Contents

Advertisement

Ingeteam Power Technology, S.A.
1.
Connection of the communications cable supplied with the equipment, to the quick connector located on
the Ingecon
µWind. The Ingecon
®
with the Ingecon
µWind.
®
connector for the
µWind ↔ Ingecon
Ingecon
®
2.
Once the push-pull connector has been inserted, screw down the hood to guarantee the IP65 insulating
rating.
Once the assembly has been completed, it will be possible to establish communications with the Ingecon
Interface through the quick connector located in the Ingecon

5.3.5. Analog inputs

The equipment has two general purpose analog inputs located in the ANA.IN connector. These inputs can be used to
connect a number of devices, such as an anemometer or thermometer.
By default, both inputs are configured as analog inputs for a current of 0-20 mA. Should this need to be changed to
voltage inputs of 0-10 V, simply disconnect bridges JP2 (analog input 1) and JP3 (analog input 2).
26
μWind Interface communication kit (AAY0089) should be requested together
®
μWind Interface
®
Ingecon
A N A .I N
μWind TL
Ingecon
®
communications quick connector
μWind with transformer
®
µWind.
®
J P 3
J P 2
Installation manual
μWind
®
AAY2000IKI06