Turn Down Calculation; Registered Trademarks - Endress+Hauser IO-Link Ceraphant PTC31B Operating Instructions Manual

Pressure switch for safe measurement and monitoring of absolute and gauge pressure
Hide thumbs Also See for IO-Link Ceraphant PTC31B:
Table of Contents

Advertisement

Document information
8
1.5

Turn down calculation

LRL
LRV
1
Calibrated/adjusted span
2
Zero point-based span
3
URL sensor
Example
• Sensor:10 bar (150 psi)
• Upper range value (URL) = 10 bar (150 psi)
Turn down (TD):
URL
TD =
|URV
-
10 bar (150 psi)
TD =
|5 bar (75 psi)
-
In this example, the TD is 2:1.
This span is based on the zero point.
1.6

Registered trademarks

is a registered trademark of the IO-Link company group.
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
1 = 2
URV
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
LRV|
= 2
0 bar (0 psi)|
3
URL
A0029545
Endress+Hauser