Echoflex Installation Guide
Light Sensor
DIP Switch 5&6
DIP switches 5 & 6 set the deadband sensitivity, which corresponds to 10%,
20%, 35%, and 50% as a percentage of the Target Lux. The low measured
light threshold is Target - (Target x Deadband%) / 100. See
the facing page
Deadband%) / 100.
10 % = Switches 5 and 6 "Off" (default setting)
20 % = Switch 5 "Off" and 6 "On"
35 % = Switch 5 "On" and 6 "Off"
60 % = Switches 5 and 6 "On"
DIP Switch 7
DIP switch 7 is not used in this product.
DIP Switch 8
DIP switch 8 provides a "restore defaults at boot" function. To restore the
factory defaults, set this DIP switch to "On" and then cycle power to the
sensor.

Power Up and Final Installation

Complete all EchoConnect terminations in the system before you apply power
to the system and sensor.

Sensor Count

The controller includes an LED labeled "Mode/Sensor Count" that blinks
green according to the number of Sensor heads connected to the controller.
Check this LED to ensure that the system has been wired properly and that
the controller has detected the number of connected remote heads. If the
Mode/Sensor Count LED is solid red, the controller does not detect any
sensors. Check your system wiring first, and then contact Echoflex Technical
Services if additional troubleshooting assistance is required.

Configure Preset

When in Basic config mode (DIP switch 2
is set to "Off"), holding the [MODE]
button sets the sensor into program
mode. Program mode only affects
switched operation and is used to adjust
the preset controlled by the dark action
when measured light levels are below
the target threshold setting. The bright
action is "Off," and occurs when measured light levels are above the target
threshold. This is not configurable through Program mode.
Light Sensor
. The high measured light threshold is Target + (Target x