Power Up and Test

Power Up
All EchoConnect terminations in the system must be made before applying
power to the system and sensor. When the sensor is powered up, the PIR LED
illuminates for one minute for calibration and warm-up, and then returns to
normal operation.
Configuration
Sensor configuration for Basic config mode (DIP switch 2 set to Off) can be
accomplished locally on the sensor using the other available DIP switches,
[MODE] button and LED, and the Auxiliary button. See
Vacancy Timeout
Preset
The [MODE] button and LED found on the rear panel of the sensor sets the
sensor into "Program Mode." Both the [MODE] button and LED, and the
Auxiliary "A" button are used for configuration of the occupancy detected
action.
The "A" button and Mode LED are used to program the preset that is
activated with an occupancy detected state change. The Mode LED blinks to
indicate the current preset number used.
Note:
Echo Occupancy/Vacancy Sensor
page 9
on
for local configuration instructions.
The occupancy detected action only matters when using the sensor
without manual wall station controls. When manual wall stations are
present in the space, the sensor will only control the vacancy action
(manual on).
Page 8 of 12