Echoflex Installation Guide
Light Sensor
Set Space and Address
Use the two rotary switches on the rear panel of the controller to set the
sensor Space and Address. By default, these switches are set to
Space 1, Address 1.
Note:
Commands are shared by all devices within a space.
DIP Switch Settings
Use the DIP switches on the rear panel of the Light Sensor controller to set
additional configuration options including deadband sensitivity, delay time,
and to restore the sensor to its factory defaults.
DIP Switch 1
DIP switch position 1 determines whether the sensor will use a Dimming
operation (Off) or a Switched operation (On). The default setting is Dimming
operation. See
DIP Switch 2
DIP switch 2 enables "Custom Config", which instructs the sensor to use
settings that are configured using the ElahoAccess Mobile App. This setting is
"Off" by default.
When "Custom Config" is set to "Off" (default setting), the controller
•
uses the local DIP switch settings for the dark and bright actions. You
can adjust sensor actions using the program [MODE] button.
When "Custom Config" is set to "On", the controller ignores local
•
DIP switch settings. Instead, the controller uses Delay Time, Deadband
Sensitivity, Switched or Dimming operation setting, dark or bright
event settings, and Dimming Raise and Lower Event settings that you
set in the ElahoAccess Mobile App.
DIP Switch 3&4
DIP switches 3 & 4 set the "Delay Time". Supported times are in minutes.
5 minutes = Switches 3 and 4 "Off" (default setting)
•
15 minutes = Switch 3 "Off" and 4 "On"
•
30 minutes = Switch 3 "On" and 4 "Off"
•
60 minutes = Switches 3 and 4 "On"
•
Light Sensor
Do not duplicate a device Address within the same Space.
Sensor Operation on page 11
.
Page 9 of 12