5. Diagnostics and error handling

5.3.1 Behaviour in response to original module errors

Channe
FP LED
l error
LED
Tab. 5/7:
Behaviour in response to module errors
5-10
Module
Error
Error description
error
no.
LED
5
Undervoltage in supply
voltage
61
Overvoltage in supply
voltage
65
Set PROFIsafe address
does not correlate with
safety parameterisation
(F_Dest_Add)
66
Error in safe
communication
67
The chronological
sequence for PROFIsafe
communication is
impaired
69
Error in safe
parameterisation (safety
parameterisation
invalid)
75
Overtemperature of
the input module
Short circuit/overload
in a clock output
145
Input module has
detected an error
during the self-test
All input channels on the input module are passivated in
response to module errors.
After remedial action: reintegrate the input module.
Remedy
Correct supply voltage or
remedy the short circuit
Correct supply voltage
Check and correct set
address/parameter
è Chapter 2.4 and 3.8
Transmit new parameters
Rectify source of error
Check the communication
paths
Check timeout time
è Chapter 3.8
Check parameters in the
PROFIsafe protocol
Transmit new parameters
Remedy overtemperature
Remedy short circuit/
overload on T0, T2, T4, T6
Switch CPX terminal on
again
Replace input module