Error Characteristics - Festo CPX Series Description

Input module
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

5. Diagnostics and error handling
5.2

Error characteristics

No. Error messages
02
Channel error short circuit 24 V
02
Module error short circuit 0 V clock
output T1357
03
Channel error wire break
05
Module error undervoltage
29
Channel error configuration
e.g. invalid function mode
55
Channel error process value
61
Module error overvoltage
65
Module error F_DEST_ADD different
5-4
The input module distinguishes between types of error and
responds accordingly with:
Channel passivation if a failure can be allocated to
precisely that channel (e.g. with detection of shorts across
contacts).
Module passivation if the error that occurs cannot be
allocated precisely to one channel and a component
defect is not detected (e.g. communication failure with
PROFIsafe).
Safe shut-down if a single microcontroller detects the
failure of a component that is required to run the
program.
Passivation as a result of the incorrect setting of
a function mode.
The input module can only transmit certain error messages as
a function of the selected function mode.
Function mode
0
ü
ü
ü
ü
1
2
3
4
5
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
Festo CPX-F8DE-P-EN en 2005b English
6
7
8
9
10
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpx-f8de-p2597424

Table of Contents