Test Function; Standards; Communications Test; Alarm/Contact Output Operation Test - Mitsubishi Electric Super-S ME96SS Series Manual

Electronic multi-measuring instrument
Table of Contents

Advertisement

Test Function

»A test function is provided to check the wiring for communication, alarm output/contact output, analog output and pulse output without
input of voltage or current.
»At the time of wiring test before shipment of the board and counter test for system validation on site, test signals can be output only
by applying the auxiliary power.
Note: Depending on the optional unit and settings, the test function may not be available (may not be displayed).

(1) Communications Test

qDisplay
»The same as for the operating mode, display patterns and other data are shown as set.
»Both maximum and minimum values can be displayed.
wCommunication data
»Communication items and value are the same one on the display. The items value that are
not displayed is 0 (zero).
»Measuring items set for alarm will be displayed at the time of an alarm.
»Input/Output contact status can be monitored.

(2) Alarm/Contact Output Operation Test

qDisplays current alarm and contact status.
wPress the Reset button for 2sec, and regardless if there is an alarm or not,
the display and contact output will operate as follows.
Status
Display
Alarm
No alarm
(3) Analog Output Operation Test
qDisplay the output items.
wPress the + or – button to change the
analog output.
Note: Default value is 0%.
(4) Pulse Output Operation Test
Press the Reset button one time to output one pulse.
Note: After reaching 50, count will return to 1.
...
0
1
2
49
Note: Default value is 0 pulses.

Standards

All products are compliant with CE Marking, UL Standards, KC mark and FCC/IC.
Output terminal
ON
ON
Open
OFF
OFF
Closed
Output
0%
25%
50%
75%
100%
100%
50 [pulse]
Output specs
4-20mA
0%
4mA
25%
8mA
50%
12mA
75%
16mA
20mA
8