4. How to Use Test Mode

Test Menu 1: Communication Test

Set the setting confirmation menu number to '9' to enter the test mode
In the test mode, the following operation is available.
Test Menu
SET
①Communication test
SET
Test Menu
Set the test menu number to 1.
*Refer to the right figure.
The communication test will be executed.
*Without current/voltage input, it is possible to monitor values other than
zero.
■Monitor values by communication
・Monitor elements and values are measuring items and values
displayed on the screen. The monitor values of measuring items that
are not displayed on the screen are zero. The power factor only is
1.000.
・The measuring items
■Display screen
■Button operation
Operation
Press
DISPLAY
Press
PHASE
Press
MAX/MIN
Press
and
simultaneously
for 2
seconds or more.
Press
SET
Note: When executing the communication test, read the following
document as well as this user's manual.
・Electronic Multi-Measuring Instrument ME Series MODBUS
Interface specifications (Reference No. LSPM-0075)
<To shift to other test menu>
⇒ Select other test menu number and then press
<To end the test mode>
Select End in the test menu number and then press
. The screen
will return to the operating mode.
SET
set to alarm are displayed as alarm generating.
As in the operating mode, the items are
displayed according to settings such as
display pattern.
The Max/Min value display is also possible.
(The cyclic display is not possible.)
Switch the display screen.
Switch phase display.
Switch between the RMS value and
distortion ratio on the harmonic screen.
Enter/Exit the Max/Min value screen.
Change the unit such as Wh or change
to lower-digit enlarged display.
Return to the test menu.