Outline and Features

Improved Measurement Functions

»Improved accuracy of active energy, reactive energy and power factor and expanded measurement ranges of harmonics and
demand values have been realized.
Optional Plug-in Modules
Model name
Analog output
4
ME-4210-SS96
ME-0040C-SS96
ME-0052-SS96
ME-0000BU-SS96
ME-0000MT-SS96
Note: Optional Plug-in Module can not be used with ME96SSEA-MB.
MODBUS
RTU System (ME96SSHA-MB/ME96SSRA-MB with ME-0052-SS96 (optional plug-in module))
®
Central monitor
RS485/USB
converter
USB
RS485 (MODBUS
RTU)
®
3
Model name
Transmission/Option specifications
MODBUS
Plug-in module (options)
ME96SSHA-MB
• Analog/Pulse/Contact output/input
(High-performance class)
• CC-Link communication
• Digital input/output (for MODBUS
• Backup (on SD card)
• MODBUS
MODBUS
Plug-in module (options)
ME96SSRA-MB
• Analog/Pulse/Contact output/input
(Standard class)
• CC-Link communication
• Digital input/output (for MODBUS
• Backup (on SD card)
• MODBUS
ME96SSEA-MB
MODBUS
(Economy class)
Pulse/Alarm output
Contact input
2
1
4
5
»MODBUS
RTU communication system optimizes computer monitoring operations
®
»Attachment of ME-0052-SS96 (optional) enables remote monitoring of the contact input signal
and on/off control of the contact output signal
»Digital input signals can be latched for over 30ms, and there is no need for external latch circuits
ME-0052-SS96
optional unit
Tripping
Closing
AL
PAL
TAL
Turning on/off breaker, etc.
®
RTU communication
RTU communication)
®
®
TCP communication
®
RTU communication
RTU communication)
®
®
TCP communication
RTU communication
®
Contact output
Transmission function
CC-Link
2
SD CARD
MODBUS
TCP
®
<MODBUS® RTU Interface Specifications>
• Max. Baud rate: 38.4kbps
• Max. Connection Distance: 1,200m
• Max. Connection Units: 31
<Optional Plug-in Module ME-0052-SS96>
• Digital Input: 5 points (24VDC)
• Digital Output: 2 points (35VDC)
Main measurement items
A, DA, V, Hz = ±0.1%
W, var, VA, PF = ±0.2%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = 31
st
-deg (max)
Rolling demand = W, var, VA
A, DA, V = ±0.2%
Hz = ±0.1%
W, var, VA, PF = ±0.5%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = 19
-deg (max)
th
Rolling demand = W, var, VA
A, DA, V = ±0.5%
Hz = ±0.2%
W, PF = ±0.5%
Wh = class 0.5S (IEC62053-22)
Harmonics = Only total