Mitsubishi Electric Super-S ME96SS Series Manual page 12

Electronic multi-measuring instrument
Table of Contents

Advertisement

Specifications
‡ME96SSEA-MB
Model name
Phase wire
Rating
Current (A)
Current demand (DA)
Voltage (V)
Active power (W)
Reactive power (var)
Apparent power (VA)
Power factor (PF)
Frequency (Hz)
Measurement
Active energy (Wh)
items and
accuracy
Reactive energy (varh)
Apparent energy (Vah)
Harmonic current (HI)
Harmonic voltage (HV)
Rolling demand (DW)
Rolling demand, reactive power (Dvar)
Rolling demand, apparent power (DVA)
Periodic Active energy (Wh)
Operating time
Analog output response time
Measuring method
No. of display digits
Display
and
segments
Display updating time interval
Communication
Available optional plug-in module
Power failure compensation
VT
Consumption
CT
(VA)
Auxiliary power circuit
Auxiliary power
Weight
Dimensions
Installation method
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Notes 1. Class values based on 100% of rated value.
Notes 2. Harmonic measurements where distortion ratio (content rate) is 100% or more may exceed ±2.0%.
11
Three phase 4-wire, Three phase 3-wire (3CT, 2CT), Single phase 3-wire, Single phase 2-wire
(common use)
Current
5AAC, 1AAC (common use)
Three phase 4-wire: 277/480VAC (max)
Three phase 3-wire: Delta connections: 220VAC (max), Star connections: 440VAC (max)
Voltage
Single phase 3-wire: 220/440VAC (max)
Single phase 2-wire: Delta connections: 220VAC (max), Star connections: 440VAC (max)
Frequency
50-60Hz (common use)
A1, A2, A3, AN, A
DA1, DA2, DA3, DAN, DA
V12, V23, V31, V
V1N, V2N, V3N, V
W1, W2, W3, ∑ W
PF1, PF2, PF3, ∑ PF
Hz
Receiving
Total
Total
Operating time 1, 2
A/V: RMS calculation, W: Digital multiplication, PF: Power ratio calculation,
Instantaneous value
Hz: Zero-cross, HI/HV: FFT
Demand value
DA: Thermal type calculation
Indicator
LCD with LED backlight
6 digits each at upper, middle, and lower line
A, DA, V, W, PF: 4 digits Hz: 3 digits
Digital display
Wh: 9 digits (6 or 12 possible) Relative harmonic content: 3 digits
Harmonic RMS value: 4 digits Operating time: 6 digits
Bar graph
21 segment bar graph, 22 segment indicator
0.5s or 1s (selectable)
MODBUS
Non-volatile memory used (items: setting value, max/min value, active energy, operating time)
Each phase 0.1VA (110VAC), 0.2VA (220VAC), 0.4VA (440VAC)
Each phase 0.1VA (5AAC)
7VA (at 110VAC), 8VA (at 220VAC), 5W (at 100VDC)
100-240VAC (±15%), 100-240VDC (-30% +15%)
0.5kg
96 (H) × 96 (W) × 90 (D)
Embedded
-5~+55°C (average operating temperature: 35°C or less per day)
0~85%RH (non condensing)
-25~+75°C (average temperature: 35°C or less per day)
0~85%RH (non condensing)
ME96SSEA-MB
Measurement items
AVG
AVG
(L-L)
AVG
(L-N)
AVG
®
RTU communication
Class
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.2%
class 0.5S (IEC62053-22)
±2.0%
±2.0%
(Reference)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents