Emergency Tape Ejection - Lucent 5ESS DRM User Manual

Distinctive remote module
Table of Contents

Advertisement

235-200-150
October 2005
Emergency Tape Ejection ( Netra
4.21
OVERVIEW
The operating system can apply a prevent media removal condition to the tape drive.
If this condition is active and the system fails, perform this procedure to remove the
DAT tape drive unit and reset the prevent media removal condition.
PROCEDURE
1.
Halt the system. See "Halt the Administrative Workstation," Procedure 4.2
2.
Remove power to the system or DAT tape drive.
For a Netra t 1120 or Netra 20 AW, see "Remove Power to Administrative
Workstation (Netra t 1120 and Netra 20), Procedure 4.7.
For a Netra 240 AW, see "Remove Power to DAT Tape Drive Unit (Netra 240)",
Procedure 4.15.
3.
Restore power to the system or DAT tape drive.
For a Netra t 1120 or Netra 20 AW, see "Restore Power to Administrative
Workstation (Netra t 1120 and Netra 20), Procedure 4.8.
For a Netra 240 AW, see "Restore Power to DAT Tape Drive Unit (Netra 240)",
Procedure 4.16.
4.
Press the UNLOAD button.
5.
For a Netra t 1120 or Netra 20 AW, verify that the emulated AM environment is
restored automatically.
6.
STOP. YOU HAVE COMPLETED THIS PROCEDURE.
1. Trademark of Sun Microsystems, Inc.
Issue 3.00L
ADMINISTRATIVE WORKSTATION MAINTENANCE
1
t 1120, Netra 20 and Netra 240)
Procedure 4.21
Page 4.21-1