NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Figure 3-32 Pin sequence of FE network cable
Step 2 Connect one end of the FE network cable to the FE port on the main control module, as
shown by 7 in
gateway, as shown in
Figure 3-33 Connecting the FE teamwork network cable
----End
3.12.4.3.2 Connecting the CAN Teamwork Cable
Context
In CAN networking, one teamwork network supports a maximum of 32 smart cooling
products. If CAN networking is required onsite, set Teamwork CAN resistor enable on the
Teamwork settings page for the first and last smart cooling products to Yes.
Issue 07 (2020-03-16)
Figure
3-30, and connect the other end to the POE port on the smart ETH
Figure
3-33.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
56