2.4 Technical Specifications

Table 2-6 Technical specifications of NetCol5000-C065
Item
Power system
Number of fans
Cooling capacity (kW)
Air volume (m
Water flow (m
Water pressure drop (kPa)
Humidification
Humidification capacity
(kg/h)
Maximum operating current
(A)
Recommended upstream
circuit breaker (A)
External dimensions (H x W
x D, mm)
Air filter level
Net weight/Gross weight
(kg)
Note: Rated working conditions are that the return air temperature is 37° C; the return air
relative humidity is 24%; the supply/return water temperatures are 10° C/15° C respectively;
and the static pressure outside the smart cooling product is 0 Pa.
Table 2-7 Technical specifications of NetCol5000-C080
Item
Power system
Number of fans
Cooling capacity (kW)
Air volume (m
Water flow (m
Issue 07 (2020-03-16)
NetCol5000-C065H9B202
0030D0
220–240 V AC, 1 PH, 50/60 Hz
10
65
3
/h)
10000
3
/h)
12
100
No
0
15
32
2000 x 600 x 1200
G4
200/234
NetCol5000-C080H9B20200
30D0
220–240 V AC, 1 PH, 50/60 Hz
12
80
3
/h)
12000
3
/h)
14
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
NetCol5000-C065H9B202
W030D0
Yes
3
202/236
NetCol5000-C080H9B2
02W030D0
23