NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Item
Water pressure drop (kPa)
Humidification
Humidification capacity
(kg/h)
Maximum operating current
(A)
Recommended upstream
circuit breaker (A)
External dimensions (H x W
x D, mm)
Air filter level
Net weight/Gross weight
(kg)
Note: Rated working conditions are that the return air temperature is 37° C; the return air
relative humidity is 24%; the supply/return water temperatures are 10° C/15° C respectively;
and the static pressure outside the smart cooling product is 0 Pa.

2.5 Performance Curves

Figure 2-10
proportion to the altitude when the NetCol5000-C works under rated power and air flow.
Cooling Capacity Derating Coefficient Curve in Proportion to the Altitude
Figure 2-10 Cooling capacity derating coefficient curve in proportion to the altitude
Issue 07 (2020-03-16)
and
Figure 2-11
When the altitude is within 1000 m, the cooling capacity deviation is in the tolerance range and can be
ignored.
Copyright © Huawei Technologies Co., Ltd.
NetCol5000-C080H9B20200
30D0
100
No
0
17
32
2500 x 600 x 1200
G4
238/268
show the cooling capacity derating coefficient curve in
2 Product Description
NetCol5000-C080H9B2
02W030D0
Yes
3
240/270