Chilled Water Inlet And Outlet Pipes; Pipe Support - Huawei NetCol5000-C Series User Manual

In-row chilled water smart cooling product
Hide thumbs Also See for NetCol5000-C Series:
Table of Contents

Advertisement

NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual

3.1.3.4 Chilled Water Inlet and Outlet Pipes

The following illustrates how to connect water inlet and outlet pipes to reserved ports on the
cabinet.
Figure 3-6 Connecting the water inlet and outlet pipes
(1) G 1–1/2 in. port with inner
threads (reserved device port)
(3) Direct connection of external
teeth (engineering purchase)
(5) Nut

3.1.3.5 Pipe Support

Supports for pipes and water pipes as shown in the figure. The actual appearance of the
supports will be different based on onsite situations.
Issue 07 (2020-03-16)
The object shown in the dotted line box is the water inlet pipe connector with inner screw threads
delivered with smart cooling products. Other parts are not provided and need to be purchased.
Copyright © Huawei Technologies Co., Ltd.
(2) Seamless steel pipe with a G 1–1/2 in. external
threaded connector (engineering purchase)
(4) Sealing ring
(6) Aluminum plastic pipe with an inner diameter of
41 mm (engineering purchase)
3 Installation
32