NetCol5000-C(065, 080) In-row Chilled Water Smart
Cooling Product
User Manual
Menu
Comm Settings
(visible for
V200R002
version)
----End
4.2 Home Screen
You can tap the menu items, buttons, or icons on the screen to enter related screens or perform
operations, such as Running, Alarms and Settings. The controller main screen is shown in
Figure
User interfaces displayed in this document are for reference only.
Issue 07 (2020-03-16)
Parameter
Cold aisle
sensor 4
Cold aisle
sensor 5
Hot aisle
sensor 1
Hot aisle
sensor 2
Hot aisle
sensor 3
Hot aisle
sensor 4
Hot aisle
sensor 5
Modbus
Comm
address
4-3.
Copyright © Huawei Technologies Co., Ltd.
Description
The sensors in hot
aisles can be set to
Enable or Disable.
Set the
communication
address of the smart
cooling product as
planned. The EMS
communicates with
the smart cooling
product through this
address.
4 Commissioning
Configuration Principle
The hot aisle sensors outside the
cabinet need to be enabled when
they are installed.
The communication addresses
of two smart cooling products
connecting to the same EMS
must be unique.
69