NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual (2019)
3.1.3.3 Chilled Water Inlet and Outlet Pipes
The following illustrates how to connect water inlet and outlet pipes to reserved
ports on the cabinet.
Figure 3-5 Connecting the water inlet and outlet pipes
(1) NetCol5000-C065: G 1–1/2 in.
port with inner threads (reserved
device port)
NetCol5000-C030/C032: G 2 in. port
with inner threads (reserved device
port)
(3) Direct connection of external
teeth (engineering purchase)
(5) Nut
3.1.3.4 Pipe Support
Supports for pipes and water pipes as shown in the figure. The actual appearance
of the supports will be different based on onsite situations.
Issue 03 (2020-08-30)
Copyright © Huawei Technologies Co., Ltd.
(2) NetCol5000-C065: Seamless steel pipe with a G 1–
1/2 in. external threaded connector (engineering
purchase)
NetCol5000-C030/C032: Seamless steel pipe with a G 1
in. external threaded connector (engineering purchase)
(4) Sealing ring
(6) NetCol5000-C065: Aluminum plastic pipe with an
inner diameter of 41 mm (engineering purchase)
NetCol5000-C030/C032: Aluminum plastic pipe with an
inner diameter of 26 mm (engineering purchase)