Installer Setup
ISU #
Name
10125
Ventilation
Priority
10130
Ventilation Low
Temperature
Lockout
10130
Ventilation
High
Temperature
Lockout
10130
Ventilation
High Dew Point
Lockout
10170
Ventilator Core
Cleaning
Reminder
10170
Ventilator Filter
Cleaning
Reminder
11000
Number of UV
Devices
11050
Replace UV
Bulb 1
11050
Replace UV
Bulb 2
Table 5. Installer Setup (ISU)
Settings
• ASHRAE is Priority
ASHRAE is
• Lockouts are
Priority
priority
Off, -20° F to 40° F in
Off
5° F increments.
(Off, -29.0° to 4.5°C in
varying increments)
Off 80° F to 110° F
Off
(in 5° F increments)
Off
Off
65° F to 85° F in 5°
F increments
(Off 26.5° C to 43.5° F
in varying increments)
Off
Off
3, 6, 9, 12 Calendar
Months
Off
Off
3, 6, 9, 12 Calendar
Months
0, 1, 2
0
Off, 6, 12, 24 Calendar
Off
Months
Off, 6, 12, 24 Calendar
Off
Months
27
T10 PRO SMART THERMOSTAT WITH REDLINK
Default
Lockouts are Priority: The thermostat places
a priority on lockouts versus the ASHRAE
62.2 ventilation standard. The thermostat
will not run ventilation during the following
lockout conditions (if configured) unless you
manually call for ventilation:
• Lockout Ventilation during Outdoor
Conditions (ISU 10130)
• Lockout Ventilation during "Sleep"
program period. Note: This option is set
by the user on the Ventilation screen in
the Menu (under options).
ASHRAE is Priority: ASHRAE requires
additional ventilation following a long off
cycle.
The thermostat meets the ASHRAE 62.2
ventilation standard by running additional
ventilation when outdoor conditions are
favorable. If ASHRAE cannot be met when
outdoor conditions are favorable, the
thermostat will override the outdoor
lockouts and run ventilation. When using
this option, it is recommended to increase
the rate (CFM) of the ventilation equipment
to meet the ASHRAE 62.2 ventilation
standard in a shorter run time.
Requires either wired outdoor sensor or
Internet weather (thermostat connected to
Wi-Fi and registered to the app).
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 10130)" beginning on
page 36.
Requires Internet weather (thermostat
connected to Wi-Fi and registered to the
app). Wired outdoor sensor doesn't enable
this setting because wired sensors don't
sense humidity.
This ISU is only displayed when ISU 10000
Ventilation Type is set to ERV / HRV or Fresh
Air Damper.
See "Ventilation — Outdoor Condition
Lockouts (ISU 10130)" page 36.
Some systems may have two UV devices,
one for the A-Coil and another for Air
Treatment. A replacement reminder can be
setup for each one. Select 0 if no UV devices
are installed.
Notes
33-00462—01