3 - OPERATION
Parameter
Par. No.
223
Repetition limit pressure switch mini-gas
225
Gas: Pre-purge time
226
Gas: Pre-ignition time
227
Gas: Safety time 1 (TSA1)
229
Gas: time to respond to pressure faults in TSA1
230
Gas: Interval 1
231
Gas: Safety time 2 (TSA2)
232
Gas: Interval 2
233
Gas: Afterburn time
234
Gas: Post purge time
237
Gas pressure switch-max / POC input
0 = deactivated
1 = pressure switch-max
2 = POC
239
Gas: Forced intermittent operation
0 = deactivated
1 = activated
240
Gas: Repetition limit loss of flame
241
Gas: Execution leakage test
0 = no leakage test
1 = leakage test on start up
2 = leakage test on shut down
3 = leakage test on both
242
Gas: Leakage test evacuation time
243
Gas: Leakage test time atm pressure
244
Gas: Leakage test filling time
245
Gas: Leakage test time gas pressure
246
Gas: Waiting time gas shortage
400
Ratio Curves
401
Ratio control curve fuel actuator
402
Ratio control curve air actuator
403
Ratio control curve VSD
500
Ratio Control
501
No-flame positions fuel actuator
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
502
No-flame positions air actuator
Index 0 = no-load position
Index 1 = pre-purge position
Index 2 = post-purge position
*Data is for reference purposes only. Fulton Companies is not responsible for this product, including (but not limited to) its accuracy, reliability, and safety. No
Fulton document should substitute for full review of documentation available from the product manufacturer.
+Out of Test Fire
Note: Customer settings should be recorded in the Customer column for reference.
3-14
VSRT_IOM_2018-1213
Table 7 - Steam Program for Siemens LMV3*
Min Value
1
20 s
0.2 s
0.2 s
0.2 s
0.2 s
0.2 s
0.2 s
0.2 s
0.2 s
1
0
1
0
0.2 s
0.2 s
0.2 s
0.2 s
0.2 s
0
0
20 %
0
0
Max Value
Fulton Setting
16
1
60 s
30 s
60 min
2 s
10 s
5 s
9.8 s
1.8 s
60 s
5 s
10 s
5 s
60 s
2.0 s
60 s
8 s
108 mi,
15 s
2
2
1
1
2
1
3
0
3 s
10s
60 s
10 s
10s
3 s
60 s
10 s
60 s
10 s
90
90
100 %
90
0
0
0
90
0
65
45
Customer