7. Make changes to the fuel profile. Three changes
will need to be made: fan output, fuel and air
settings. To make changes:
» Safely drive the unit to the high-fire position,
P9, by pressing the "+" button to proceed from
P0 through P9.
» Check the O2 level in the stack outlet.
» Once the desired O2 level and input (last elbow
pressure) is reached, proceed to the next
combustion point until all points have been set.
8. Back out to the front screen by pressing the "–"
and "+" buttons together.
O f f U P r
S E r
9 5 4
:
0
7 0 1
:0 1: 6 2
7 0 1
:0 1: 6 2
7 0 1:
0 1
: 6 2
7 0 1:
02
:
0
7 0 1:
03
:
0
7 0 1:
04
:
10
7 0 1:
05
: 22
7 0 1:
06
: ._._
7 0 1:
07
:
0
- E n d -
7 0 1
:0 1: 6 2
7 0 2
:0 1: 8 7
7 0 2:
0 1
: 8 7
7 0 2:
0 2
: 1
3-6
VSRT_IOM_2018-1213
ADJUSTING THE PROFILE
! WARNING
This information is for reference purposes only. Fulton
Companies is not responsible for this product, including
(but not limited to) its accuracy, reliability, and safety.
No Fulton document should substitute for full review of
documentation available from the product manufacturer.
See the table, below, for a Siemens LMV3 fault history
listing. Refer to Table 7 at the end of this section of this
manual for Siemens LMV3 parameter information.
Fault History
Key:
Red
indicates "Flashing"
Hold until Ser is displayed, and release
1st parameter shown is flame signal
+ until parameter 701 is displayed
(701 is the most recent fault, 725 is the oldest)
Each fault has "indexes" for more information
In this example, "62" is the
Hold Return, until index "01" flashes,
+ to display parameter 701, index "02"
In this example "0" is the
+ to display parameter 701, index "03"
In this example "0" is the
+ to display parameter 701, index "04"
In this example "10" is the
+ to display parameter 701, index "05"
In this example "22" is the
+ to display parameter 701, index "06"
In this example "._._"indicates no
+ to display parameter 701, index "07"
In this example "0" is the
+ at this point displays - End - ,
to indicate that there are no more "indexes"
Esc to go back to parameter 701:01
Hold Return, until index "01" flashes,
+ to display parameter 702, index "02"
In this example "1" is the
(Momentarily displayed)
(parameter 954)
Error code
and release
Diagnostic code
Class
(UK use ONLY)
Phase
Startup number
Load
Fuel
(Fuel 0, or Fuel 1)
+ to display parameter 702
and release
Diagnostic code
(firing rate)