SCREENED INLET
IF SNOW ACCUMULATION
IS APPLICABLE, OPENING TO BE
1 FT. / 30 CM ( MIN. ) ABOVE
THIS NORMALLY EXPECTED LEVEL.
AIR INLET
EXHAUST PIPE
WALL PENETRATION
48 IN. / 122 CM.
(MINIMUM)
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
EXHAUST OUTLET
MIN 4FT
( 122 CM )
MIN 4FT / 122 CM
ABOVE AIR
INTAKE PIPING
APPROVED EXHAUST
VENT MATERIAL
VSRT
AIR INTAKE & EXHAUST PIPES WALL PENETRATION CLEARANCES
BOILER
( SIDE VIEW )
10 FEET
(MINIMUM)
LOCATE INTAKE
EXHAUST PIPING
AIR INTAKE
WALL PENETRATION
WIND DIRECTION
Figure 17 - Side Wall Penetration Details
NOTE:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS.
EXHAUST STACK IS DOWNWIND
OF AIR INTAKE OPENING
DO NOT PLACE INSULATION IN
REQUIRED AIR SPACE CLEARANCE
BAND SUPPORT
(TYP EACH SIDE)
RISE TO RUN: 1/4" PER FOOT
APPROVED EXHAUST
VENT MATERIAL
CAUTION:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS
UPWIND OF
NOTE:
MAINTAIN MINIMUM 9"/22.86 CM AIR SPACE
CLEARANCES TO COMBUSTABLES, WIRES AND INSULATION
NOTE:
1.) When using horizontal runs follow a 1/4" per foot rise to run ratio
2.) Maintain minimum 9" / 22.86 cm air space clearances to combustables,
wires and insulation
3.) Install support straps at 5 FT / 152 CM horizontal intervals and at elbows
INSTALLATION - 2
WALL
TYPICAL ROOF PENETRATIONS
( SUGGESTED TERMINATION CONFIGURATIONS )
WALL TERMINATION
( WITH SCREEN )
4 FT / 122 CM ( MINIMUM )
BETWEEN INLET & EXHAUST
OPENING ( SEE BELOW )
AIR INTAKE AND EXHAUST
COLLAR
TERMINATION SHOULD BE
SEPERATED AS FAR AS POSSIBLE
TO PREVENT FLUE GAS
RECIRCULATION DURING
DIFFERENT WIND CONDITIONS.
6 IN / 15 CM
MIN
OPENING 1 FT / 30 CM ( MIN )
ABOVE NORMALLY EXPECTED
90° ELBOW
SNOW ACCUMULATION LEVEL
SCREENED AIR INLET
VSRT_IOM_2018-1213
2-33